3-36 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
3.5.1.7 Intermediate GOOSE subscription objects (GGIO3)
GGIO3 is instantiated in all UR family devices.
Table 3-16: Intermediate GOOSE subscription data objects
3.5.1.8 FlexAnalog operand interface (GGIO4)
GGIO4 is instantiated in all UR family devices.
Table 3-17: FlexAnalog data objects
stVal BOOLEAN ST FlexLogic operand Virt Ip ψ On R
pulseConfig PulseConfig CF R
pulseConfig
.cmdQual
ENUMERATED 0 (pulse) R
pulseConfig.onDur INT32U 0 indicates the duration is locally defined R
pulseConfig
.offDur
INT32U 0 R
pulseConfig
.numPls
INT32U 1 R
ctlModel CtlModels CF GGIO2 CF SPCSO ψ CTLMODEL R/C
sboTimeout INT32U CF 30000 R
sboClass SboClasses CF 0 (operate-once) R
operTimeout INT32U CF 0 R
LNName: GGIO3 LDevice inst: Master UR element: RxGOOSE Inputs
data obj. data attribute Type FC UR Name Description R/W/C
Indψψψ SPS RxGOOSE Booleanψ operand R
stVal BOOLEAN ST RxGOOSE Booleanψ On R
IndPosψψ DPS RxGOOSE DPSψ actual value R
stVal CODED ENUM ST R
OpnStψψ SPS RxGOOSE DPSψ Off operand R
stVal BOOLEAN ST FlexLogic operand RxGOOSE
DPSψ Off
R
ClsStψψ SPS RxGOOSE DPSψ On operand R
stVal BOOLEAN ST FlexLogic operand RxGOOSE
DPSψ On
R
BadStψψ SPS RxGOOSE DPSψ Bad operand R
stVal BOOLEAN ST FlexLogic operand RxGOOSE
DPSψ Bad
R
IntermStψ
ψ
SPS RxGOOSE DPSψ INTERM operand R
stVal BOOLEAN ST FlexLogic operand RxGOOSE
DPSψ Interm
R
AnInψψ MV RxGOOSE Analogψ operand R
mag AnalogueValue MX R
mag.f FLOAT32 RxGOOSE Analog In ψ R
units.SIUnit ENUMERATED RxGOOSE Analog # UNITS R
units.multiplier ENUMERATED RxGOOSE Analog # UNITS R
LNName: <configured GGIO4
prefix>GGIO4
LDevice inst: Master UR element: FlexAnalog Operand Interface functionality
data obj. data attribute Type FC UR Name Description R/W/C
AnInψψ MV OFF R
instMag AnalogueValue MX
R
LNName: <configured GGIO2
prefix>GGIO2
LDevice inst: Master UR element: Generic controllable single point
data obj. data attribute Type FC UR Name Description R/W/C