3-40 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
Table 3-23: B90 breaker failure logic data objects
LNName: B_BFaiRBRF# LDevice inst: Prot UR element: B90 BREAKER FAILURE logic element
data obj. data attribute Type FC UR Name Description R/W/C
OpEx ACT BKRFAIL # TRIP OP operand R
general BOOLEAN ST BKRFAIL # TRIP OP R
OpIn ACT BKRFAIL # RETRIP operand R
general BOOLEAN ST re-trip operand BKRFAIL #
RETRIP
R
BkrOp& SPS BKRFAIL # T& OP operand R
stVal BOOLEAN ST BKRFAIL # T& OP R
InRefγ01 ORG BF# INITIATE setting for setting group γ.R
setSrcRef ObjectReference SP BF# INITIATE for group γ. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRefγ02 ORG BF# AMP SUPV OP A setting for setting
group γ.
R
setSrcRef ObjectReference SP BF# AMP SUPV OP A for group γ.reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRefγ03 ORG BF# AMP SUPV OP B setting for setting
group γ.
R
setSrcRef ObjectReference SP BF# AMP SUPV OP B for group γ.reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRefγ04 ORG BF# AMP SUPV OP C setting for setting
group γ.
R
setSrcRef ObjectReference SP BF# AMP SUPV OP C for group γ.reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRefγ05 ORG BF# BKR POS1 setting for setting group γ.R
setSrcRef ObjectReference SP BF# BKR POS1 for group γ. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRefγ06 ORG BF# BKR POS2 setting for setting group γ.R
setSrcRef ObjectReference SP BF# BKR POS2 for group γ. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRefγ07 ORG BF# BKR TEST ON setting for setting
group γ.
R
setSrcRef ObjectReference SP BF# BKR TEST ON for group γ. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRefγ08 ORG BF# AMP HISET OP A setting for setting
group γ.
R
setSrcRef ObjectReference SP BF# AMP HISET OP A for group γ.reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRefγ09 ORG BF# AMP HISET OP B setting for setting
group γ.
R
setSrcRef ObjectReference SP BF# AMP HISET OP B for group
γ.reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRefγ10 ORG BF# AMP HISET OP C setting for setting
group γ.
R
setSrcRef ObjectReference SP BF# AMP HISET OP C for group γ.reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRefγ11 ORG BF# AMP LOSET OP A setting for setting
group γ.
R
setSrcRef ObjectReference SP BF# AMP LOSET OP A for group
γ.
reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRefγ12 ORG BF# AMP LOSET OP B setting for setting
group γ.
R
setSrcRef ObjectReference SP BF# AMP LOSET OP B for group
γ.
reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRefγ13 ORG BF# AMP LOSET OP C setting for setting
group γ.
R

Table of Contents