3-42 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
3.5.2.7 B90 end fault protection (B_Efp)
This element is instantiated in the following products: B90.
Table 3-25: B90 end fault protection data objects
instCVal.mag.f FLOAT32 BUS ZONE # REST current
magnitude
R
instCVal.ang.f FLOAT32 BUS # REST current angle UR range -180...+180 converted to 0...360 R
cVal Vector MX R
cVal.mag.f FLOAT32 instCVal.mag.f deadbanded R
cVal.ang.f FLOAT32 instCVal.ang.i deadbanded R
units Unit CF R
units.SIUnit ENUMERATED 5, the code for primary amperes R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
db INT32U CF B_DifPDIF#.BRstA.db R/W/C
dbAng INT32U CF B_DifPDIF#.BRstA.dbAng R/W/C
zeroDb INT32U CF R
R
R
R
InRefγ01 ORG BUS ZONE # DIFF SUPV setting for setting
group γ.
R
setSrcRef ObjectReference SP BUS ZONE # DIFF SUPV for
group γ.
reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRefγ02 ORG BUS ZONE # DIFF TRIP setting for setting
group γ.
R
setSrcRef ObjectReference SP BUS ZONE # DIFF TRIP for group
γ.
reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
BlkRefγ ORG BUS ZONE # DIFF BLK setting for setting
group γ.
R
setSrcRef ObjectReference SP BUS ZONE # DIFF BLK for group
γ.
reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef9ττ ORG BUS ZONE #τ STATUS setting. R
setSrcRef ObjectReference SP BUS ZONE #τ STATUS setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: B_EfpPIOC# LDevice inst: Prot UR element: B90 End fault protection element # function
data obj. data attribute Type FC UR Name Description R/W/C
Str ACD EFP # PKP operand R
general BOOLEAN ST EFP # PKP R
dirGeneral ENUMERATED ST 0, the code for unknown. It is unknown as
the element is non-directional
R
Op ACT EFP # OP operand R
general BOOLEAN ST EFP # OP R
Dpo SPS EFP # DPO operand, which is the inverse
of EFP PKP
R
stVal BOOLEAN ST EFP # DPO R
InRefγ1 ORG EFP# BREAKER OPEN setting for setting
group γ.
R
setSrcRef ObjectReference SP EFP# BREAKER OPEN for group
γ.
reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRefγ2 ORG EFP# MANUAL CLOSE setting for setting
group γ.
R
LNName: B_DifPDIF# LDevice inst: Prot UR element: B90 Bus zone # differential element function
data obj. data attribute Type FC UR Name Description R/W/C