3-44 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
Table 3-28: B90 undervoltage data objects
3.5.2.11 Breaker failure (BkrFa)
This element is instantiated in the following products: B30, C60, C70, D60, F60, G60, L30, L60, L90, M60, T60.
Table 3-29: Breaker failure data objects
LNName: B_UvPTUV# LDevice inst: Prot UR element: B90 Undervoltage element # function
data obj. data attribute Type FC UR Name Description R/W/C
Str ACD UNDERVOLTAGE # PKP operands R
general BOOLEAN ST UNDERVOLTAGE # PKP R
dirGeneral ENUMERATED ST 0, the code for unknown. It is unknown as
the element is non-directional
R
Op ACT UNDERVOLTAGE # OP operand R
general BOOLEAN ST UNDERVOLTAGE # OP R
Dpo SPS UNDERVOLTAGE # DPO operand, which is
the inverse of UNDERVOLTAGE PKP
R
stVal BOOLEAN ST UNDERVOLTAGE # DPO R
BlkRefγ ORG UNDERVOLTAGE # BLK setting for setting
group γ.
R
setSrcRef ObjectReference SP UNDERVOLTAGE # BLK for group
γ.
reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: BkrFaRBRF# LDevice inst: Prot UR element: Breaker Control element #
data obj. data attribute Type FC UR Name Description R/W/C
InRefγ02 ORG BF# 3-POLE INITIATE setting for setting
group γ
R
setSrcRef ObjectReference SP 3-POLE INITIATE input reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
BlkRefγ ORG BF# BLOCK setting for setting group γ R
setSrcRef ObjectReference SP BF# BLOCK. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRefγ03 ORG BF# BKR POS1 φA/3P setting for setting
group γ
R
setSrcRef ObjectReference SP BF# BKR POS1 φA/3P. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRefγ04 ORG BF# BKR POS2 φA/3P setting for setting
group γ
R
setSrcRef ObjectReference SP BF# BKR POS2 φA/3P. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRefγ05 ORG BF# BKR POS1 φB setting for setting
group γ
R
setSrcRef ObjectReference SP BF# BKR POS1 φB. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRefγ06 ORG BF# BKR POS1 φC setting for setting
group γ
R
setSrcRef ObjectReference SP BF# BKR POS1 0C. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRefγ07 ORG BF# BKR POS2 φB setting for setting
group γ
R
setSrcRef ObjectReference SP BF# BKR POS2 φB. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRefγ08 ORG BF# BKR POS2 φC setting for setting
group γ
R
setSrcRef ObjectReference SP BF# BKR POS2 φC. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
OpIn ACT BKR FAIL # RETRIP operands R
general BOOLEAN ST re-trip operand BKR FAIL #
RETRIP
R

Table of Contents