3-50 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
Table 3-35: Compensated overvoltage stage data objects
3.5.2.16 Continuous monitor (CnMntr)
This element is instantiated in the following products: L90.
Table 3-36: Continuous monitor data objects
3.5.2.17 Current (amp) unbalance (AmpUnb)
This element is instantiated in the following products: M60.
Table 3-37: Current unbalance data objects
LNName: CmpOvPTOV$ LDevice inst: Prot UR element: Compensated Overvoltage stage $
data obj. data attribute Type FC UR Name Description R/W/C
Str ACD COMP OV STG$ PKP operand R
general BOOLEAN ST COMP OV STG$ PKP R
dirGeneral ENUMERATED ST 0, the code for unknown. It is unknown as
the element is non-directional
R
Op ACT COMP OV STG$ OP operand R
general BOOLEAN ST COMP OV STG$ OP R
Dpo SPS COMP OV STG$ DPO operand, which is
the inverse of COMP OV STG$ PKP
R
stVal BOOLEAN ST COMP OV STG$ DPO R
LNName: CnMntrGAPC1 LDevice inst: Prot UR element: Continuous Monitor element
data obj. data attribute Type FC UR Name Description R/W/C
Str ACD CONT MONITOR PKP operand R
general BOOLEAN ST CONT MONITOR PKP R
dirGeneral ENUMERATED ST 0, the code for unknown R
Op ACT CONT MONITOR OP operand R
general BOOLEAN ST CONT MONITOR OP R
InRef1 ORG CONT MONITOR I-OP setting. R
setSrcRef ObjectReference SP CONT MONITOR I-OP setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef2 ORG CONT MONITOR I-SUPV setting. R
setSrcRef ObjectReference SP Reference to the data object
selected by CONT MONITOR I-
SUPV
reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef3 ORG CONT MONITOR V-OP setting. R
setSrcRef ObjectReference SP Reference to the data object
selected by CONT MONITOR V-
OP
reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef4 ORG CONT MONITOR V-SUPV setting. R
setSrcRef ObjectReference SP Reference to the data object
selected by CONT MONITOR V-
SUPV
reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: AmpUnbPTOC# LDevice inst: Prot UR element: Amp Unbalance element
data obj. data attribute Type FC UR Name Description R/W/C
Str ACD AMP UNBALANCE # PKP operand R
general BOOLEAN ST AMP UNBALANCE # PKP R
dirGeneral ENUMERATED ST 0, the code for unknown. R