3-66 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
neut.cVal.mag.f FLOAT32 IG RESTR. CURRENT magnitude,
in primary amps, with deadband
R
neut.units Unit CF R
neut.units.SIUnit ENUMERATED 5, the code for amps R
neut.units
.multiplier
ENUMERATED 0, the code for a multiplier of 1 R
neut.db INT32U CF LinDfPDIF1.DifAClc.neut.db R/W/C
neut.zeroDb INT32U CF CURRENT CUT-OFF LEVEL setting
multiplied by 100000/46.
R
angRef ENUMERATED CF See UR product manual regarding
FREQUENCY AND PHASE REFERENCE
R
InRef001 ORG CHNL ASYM COMP setting. R
setSrcRef ObjectReference SP CHNL ASYM COMP setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
BlkRef9 ORG BLOCK GPS TIME REF setting. R
setSrcRef ObjectReference SP BLOCK GPS TIME REF setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
BlkRefγ ORG CURRENT DIFF BLOCK setting of setting
group γ.
R
setSrcRef ObjectReference SP CURRENT DIFF BLOCK setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRefγ05 ORG CURRENT DIFF KEY DTT setting of setting
group γ.
R
setSrcRef ObjectReference SP CURRENT DIFF KEY DTT setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRefγ06 ORG STUB BUS DISCONNECT setting of setting
group γ.
R
setSrcRef ObjectReference SP STUB BUS DISCONNECT setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRefγ07 ORG STUB BUS TRIGGER setting of setting
group γ.
R
setSrcRef ObjectReference SP STUB BUS TRIGGER setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRefγ08 ORG DD NON-CURRENT SUPV setting. R
setSrcRef ObjectReference SP DD NON-CURRENT SUPV setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRefγ09 ORG DD CONTROL LOGIC setting of setting
group γ.
R
setSrcRef ObjectReference SP DD CONTROL LOGIC setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRefγ10 ORG DD LOGIC SEAL-IN setting of setting
group γ.
R
setSrcRef ObjectReference SP DD LOGIC SEAL-IN setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRefγ12 ORG only instantiated in L90 R
setSrcRef ObjectReference SP 87L TRIP SUPV setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRefγ13 ORG only instantiated in L90 R
setSrcRef ObjectReference SP 87L TRIP FORCE 3-φ setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: LinDfPDIF1 LDevice inst: Prot UR element: Line Differential element (ANSI 87L) phase and general
functions
data obj. data attribute Type FC UR Name Description R/W/C

Table of Contents

Other manuals for GE b30