EasyManua.ls Logo

GE b30 - Page 316

GE b30
532 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3-78 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
3.5.2.44 Neutral instantaneous overcurrent (NeuIoc)
This element is instantiated in the following products: B30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, N60,
T60.
Table 3-74: Neutral instantaneous overcurrent data objects
3.5.2.45 Neutral overvoltage (NeuOv)
This element is instantiated in the following products: B30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, T60.
Table 3-75: Neutral overvoltage data objects
3.5.2.46 Neutral time overcurrent (NeuToc)
This element is instantiated in the following products: B30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, N60,
T60.
Table 3-76: Neutral time overcurrent data objects
LNName: NeuIocPIOC# LDevice inst: Prot UR element: Neutral Instantaneous Overcurrent element #
data obj. data attribute Type FC UR Name Description R/W/C
Str ACD NEUTRAL IOC# PKP operand, which
indicates Op will operate when delay
expires.
R
general BOOLEAN ST NEUTRAL IOC# PKP R
dirGeneral ENUMERATED ST 0, the code for unknown. R
Op ACT NEUTRAL IOC# OP operand R
general BOOLEAN ST NEUTRAL IOC# OP R
Dpo SPS NEUTRAL IOC# DPO operand R
stVal BOOLEAN ST NEUTRAL IOC# DPO R
BlkRefγ1 ORG NEUTRAL IOC# BLOCK setting in setting
group γ.
R
setSrcRef ObjectReference SP NEUTRAL IOC# BLOCK. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: NeuOvPTOV# LDevice inst: Prot UR element: Neutral Overvoltage element # functions
data obj. data attribute Type FC UR Name Description R/W/C
Str ACD NEUTRAL OV# PKP operands R
general BOOLEAN ST NEUTRAL OV# PKP R
dirGeneral ENUMERATED ST 0, the code for unknown. It is unknown as
the element is non-directional
R
Op ACT NEUTRAL OV# OP operand R
general BOOLEAN ST NEUTRAL OV# OP R
Dpo SPS NEUTRAL OV# DPO operand, which is the
inverse of NEUTRAL OV PKP
R
stVal BOOLEAN ST NETRAL OV# DPO R
BlkRefγ ORG NEUTRAL OV# BLK setting for setting
group γ.
R
setSrcRef ObjectReference SP NEUTRAL OV# BLK for group γ. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: NeuTocPTOC# LDevice inst: Prot UR element: Neutral Time Overcurrent element #
data obj. data attribute Type FC UR Name Description R/W/C
Str ACD NEUTRAL TOC# PKP operand, which
indicates that Op operates when delay
expires
R
general BOOLEAN ST NEUTRAL TOC# PKP R
dirGeneral ENUMERATED ST 0, the code for unknown R
Op ACT NEUTRAL TOC# OP operand R

Table of Contents

Other manuals for GE b30