CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE 3-83
3
3.5.2.51 Permissive overreaching transfer trip 1 (POTT1_)
This element is instantiated in the following products: D60, L90.
Table 3-83: POTT1 data objects
setSrcCB ObjectReference SP Source GoCB of input if via GOOSE R/C
InRef3 ORG POTT RX3 setting R
setSrcRef ObjectReference SP POTT RX3 Reference to the data attribute to input R/C
setSrcCB ObjectReference SP Source GoCB of input if via GOOSE R/C
InRef4 ORG POTT RX4 setting R
setSrcRef ObjectReference SP POTT RX4 Reference to the data attribute to input R/C
setSrcCB ObjectReference SP Source GoCB of input if via GOOSE R/C
LNName: POTT1_PSCH1 LDevice inst: Prot UR element: Permissive Over-reaching Transfer Trip 1 element
data obj. data attribute Type FC UR Name Description R/W/C
Op ACT POTT1 OP operand R
general BOOLEAN ST POTT1 OP R
phsA BOOLEAN ST POTT1 TRIP A R
phsB BOOLEAN ST POTT1 TRIP B R
phsC BOOLEAN ST POTT1 TRIP C R
Tr3p ACT Instantiated only on products with single
pole tripping.
R
general BOOLEAN ST POTT1 TRIP 3P R
Tx1 SPS POTT1 TX1 operand R
stVal BOOLEAN ST POTT1 TX1 R
Tx2 SPS Instantiated only on products with single
pole tripping.
R
stVal BOOLEAN ST POTT1 TX2 R
Tx3 SPS Instantiated only on products with single
pole tripping.
R
stVal BOOLEAN ST POTT1 TX3 R
Tx4 SPS Instantiated only on products with single
pole tripping.
R
stVal BOOLEAN ST POTT1 TX4 R
BlkRef1 ORG POTT1 SCHEME BLOCK setting. R
setSrcRef ObjectReference SP POTT1 SCHEME BLOCK. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef5 ORG POTT1 ECHO COND setting. R
setSrcRef ObjectReference SP POTT1 ECHO COND reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef6 ORG DIR FWD1 setting. R
setSrcRef ObjectReference SP DIR FWD1 reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef7 ORG DIR FWD2 setting. R
setSrcRef ObjectReference SP DIR FWD 2 reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef8 ORG DIR FWD3 setting. R
setSrcRef ObjectReference SP DIR FWD3 reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef1 ORG POTT1 RX1 setting. R
setSrcRef ObjectReference SP POTT1 RX1 reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: POTT_PSCH1 LDevice inst: Prot UR element: Permissive Over-reaching Transfer Trip element