3.5.2.65 RTD (PRTDs)
This element is instantiated in the following products: G60, M60, T60.
Table 3-110: RTD data objects
net.cVal Vector MX R
net.cVal.mag.f FLOAT32 RGF# DIFF Igd magnitude, in
primary amps, with deadband
R
net.units Unit CF R
net.units.SIUnit ENUMERATED 5, the code for amps R
net.units
.multiplier
ENUMERATED 0, the code for a multiplier of 1 R
net.db INT32U CF RgDifPDIF#.DifAClc.net.db R/W/C
net.zeroDb INT32U CF R
RstA WYE Restraint currents R
net CMV R
net.instCVal Vector MX R
net.instCVal.mag
.f
FLOAT32 RGF# RESTR Igr magnitude, in
primary amps
R
net.cVal Vector MX R
net.cVal.mag.f FLOAT32 RGF# RESTR Igr magnitude, in
primary amps, with deadband
R
net.units Unit CF R
net.units.SIUnit ENUMERATED 5, the code for amps R
net.units
.multiplier
ENUMERATED 0, the code for a multiplier of 1 R
net.db INT32U CF RgDifPDIF#.RstA.net.db R/W/C
net.zeroDb INT32U CF R
BlkRefγ ORG RESTD GND FT# BLOCK for setting group
γ.
R
setSrcRef ObjectReference SP RESTD GND FT# BLOCK for
group γ.
reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: PRTDsSTMP# LDevice inst: Prot UR element: RTD Input φ
data obj. data attribute Type FC UR Name Description R/W/C
Mod INC This logical node’s mode R/Ctrl
stVal ENUMERATED ST 1 (on) R
ctlModel CtlModels CF 0 (status only) R
Health INS This logical node’s health R
stVal ENUMERATED ST LPHD1.PhyHealth.stVal R
Str ACD RTD Ip # TRIP PKP operand R
general BOOLEAN ST RTD Ip # TRIP PKP R
dirGeneral ENUMERATED ST 0 R
StrAlm ACD RTD Ip # ALARM PKP operand R
general BOOLEAN ST RTD Ip # ALARM PKP R
dirGeneral ENUMERATED ST 0 R
Trip SPS RTD Ip # TRIP OP operand R
stVal BOOLEAN ST RTD Ip # TRIP OP R
Alm SPS RTD Ip # ALARM OP operand R
stVal BOOLEAN ST RTD Ip # ALARM OP R
Dpo SPS RTD Ip # TRIP DPO operand R
stVal BOOLEAN ST RTD Ip # TRIP DPO R
DpoAlm SPS RTD Ip # ALARM DPO operand R
LNName: RgDifPDIF# LDevice inst: Prot UR element: Restricted Ground Fault # function
data obj. data attribute Type FC UR Name Description R/W/C