CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE 3-115
3
Table 3-131: Voltage differential stage objects
3.5.2.82 Volts per Hertz (VpHz)
This element is instantiated in the following products: G30, G60, L90, T60.
Table 3-132: Volts per Hertz data objects
3.5.2.83 VT fuse failure (Vtff)
This element is instantiated in the following products: C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, N60, T60.
Table 3-133: VT fuse failure data objects
LNName: VDif$PDIF# LDevice inst: Prot UR element: Voltage Differential element # stage $
data obj. data attribute Type FC UR Name Description R/W/C
Str ACD VOLT DIF # STG$ PKP operands (including
individual three phases)
R
general BOOLEAN ST Logical OR of data attributes
phsA, phsB and phsC
R
dirGeneral ENUMERATED ST 0, the code for unknown R
phsA BOOLEAN ST VOLT DIF # STG$A PKP R
dirPhsA ENUMERATED ST 0, the code for unknown R
phsB BOOLEAN ST VOLT DIF # STG$B PKP R
dirPhsB ENUMERATED ST 0, the code for unknown R
phsC BOOLEAN ST VOLT DIF # STG$C PKP R
dirPhsC ENUMERATED ST 0, the code for unknown R
Op ACT VOLT DIF # STG$ OP operands R
general BOOLEAN ST Logical OR of data attributes
phsA, phsB, phsC
R
phsA BOOLEAN ST VOLT DIF # STG$A OP R
phsB BOOLEAN ST VOLT DIF # STG$B OP R
phsC BOOLEAN ST VOLT DIF # STG$C OP R
BlkRefγ ORG VOLT DIF # BLK STG$ setting for setting
group γ.
R
setSrcRef ObjectReference SP VOLT DIF # BLK STG$ for group
γ.
reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: VpHzPVPH# LDevice inst: Prot UR element: Volts per Hertz element #
data obj. data attribute Type FC UR Name Description R/W/C
Op ACT VOLTS PER HERTZ # OP operand R
general BOOLEAN ST VOLTS PER HERTZ # OP R
Dpo SPS VOLTS PER HERTZ # DPO operand R
stVal BOOLEAN ST VOLTS PER HERTZ # DPO R
Str ACD VOLTS PER HERTZ # PKP operand R
general BOOLEAN ST VOLTS PER HERTZ # PKP operand R
dirGeneral ENUMERATED ST 0 R
BlkRefγ ORG VOLTS /HZ # BLOCK setting for setting
group γ
R
setSrcRef ObjectReference SP VOLTS/HZ # BLOCK for group γ Reference to the data attribute to input R/C
setSrcCB ObjectReference SP Source GoCB of input if via GOOSE R/C
LNName: VtffGAPC# LDevice inst: Prot UR element: VT FUSE FAILURE # function
data obj. data attribute Type FC UR Name Description R/W/C
FuFail SPS SRC# VT FUSE FAIL OP operands R
stVal BOOLEAN ST SRC# VT FUSE FAIL OP R
Dpo SPS SRC# VT FUSE FAIL DPO operand, R

Table of Contents