3-126 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
mag AnalogueValue MX R
mag.f FLOAT32 instMag.f deadbanded R
units Unit CF R
units.SIUnit ENUMERATED 4, the code for time (s) R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
db INT32U CF CapCtlGAPC#.DschTms.db R/W/C
zeroDb INT32U CF 0 R
InRef01 ORG CAP # SET REMOTE 1 setting. R
setSrcRef ObjectReference SP CAP # SET REMOTE 1 setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef02 ORG CAP # SET REMOTE 2 setting. R
setSrcRef ObjectReference SP CAP # SET REMOTE 2 setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef03 ORG CAP # SET LOCAL 1 setting. R
setSrcRef ObjectReference SP CAP # SET LOCAL 1 setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef04 ORG CAP # SET LOCAL 2 setting. R
setSrcRef ObjectReference SP CAP # SET LOCAL 2 setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef05 ORG CAP # RMT CTRL EN setting. R
setSrcRef ObjectReference SP CAP # RMT CTRL EN setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef06 ORG CAP # LCL CTRL EN setting. R
setSrcRef ObjectReference SP CAP # LCL CTRL EN setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef07 ORG CAP # RMT SET AUTO setting. R
setSrcRef ObjectReference SP CAP # RMT SET AUTO setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef08 ORG CAP # LCL SET AUTO setting. R
setSrcRef ObjectReference SP CAP # LCL SET AUTO setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef09 ORG CAP # RMT SET MAN setting. R
setSrcRef ObjectReference SP CAP # RMT SET MAN setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef10 ORG CAP # LCL SET MAN setting. R
setSrcRef ObjectReference SP CAP # LCL SET MAN setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef1$ ORG CAP # TRIP $ setting. R
setSrcRef ObjectReference SP CAP # TRIP $ setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef21 ORG CAP # AUTO CTRL EN setting. R
setSrcRef ObjectReference SP CAP # AUTO CTRL EN setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef22 ORG CAP # MAN CTRL EN setting. R
setSrcRef ObjectReference SP CAP # MAN CTRL EN setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef23 ORG CAP # REMOTE OPEN setting. R
setSrcRef ObjectReference SP CAP # REMOTE OPEN setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: CapCtlGAPC# LDevice inst: Ctrl UR element: Capacitor control element #