3-132 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
phsC BOOLEAN ST HI-Z IOC C R
neut BOOLEAN ST HI-Z IOC N R
LossLd ACT HI-Z LOSS OF LOAD operand including
Phases A, B, C.
R
general BOOLEAN ST OR logic of operands HI-Z LOSS
OF LOAD-A or HI-Z LOSS OF
LOAD–B or HI-Z LOSS OF LOAD-C
R
phsA BOOLEAN ST HI-Z LOSS OF LOAD-A R
phsB BOOLEAN ST HI-Z LOSS OF LOAD–B R
phsC BOOLEAN ST HI-Z LOSS OF LOAD-C R
HiZSt ENS HIZ STATUS actual value R
stVal ENUMERATED ST HIZ STATUS, where 0 = Normal, 1
= Coordination Timeout, 2 =
Armed, 5 = Arcing, 9 = Downed
Conductor, actual values
R
ArcConfid
Φ
INS HIZ Phase Φ Arc Conf Actual Value R
stVal INT32 ST HIZ Phase Φ Arc Conf in
percentage
R
units Unit CF R
units.SIUnit ENUMERATED 1, the code for dimensionless R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
Trigger1$ ENS HIZ RECORDS, HIZ $ actual value R
stVal ENUMERATED ST HI-Z Capture $ Trigger Type,
where 0 = None, 1 = Loss of
Load, 2 = Arc Suspected, 3 =
Arcing, 4 = Overcurrent, 5 =
Down Conductor, 6 = External
R
Trigger2$ ENS HIZ RECORDS, RMS $ actual value R
stVal ENUMERATED ST HI-Z RMS Capture $ Trigger Type,
where 0 = None, 1 = Loss of
Load, 2 = Arc Suspected, 3 =
Arcing, 4 = Overcurrent, 5 =
Down Conductor, 6 = External
R
ClrMem SPC Hi-Z Clear Oscillography command R/Ctrl
pulseConfig PulseConfig CF R
pulseConfig
.cmdQual
ENUMERATED 0 (pulse) R
pulseConfig.onDur INT32U 2 ms (actually one pass) R
pulseConfig
.offDur
INT32U 0 R
pulseConfig
.numPls
INT32U 1 R
ctlModel CtlModels CF HiZPHIZ1.ClrMem.ctlModel R/W/C
sboTimeout INT32U CF 30000 R
sboClass SboClasses CF 0 (operate-once) R
operTimeout INT32U CF 0 R
FrcTrigger SPC Hi-Z Oscillography Force Trigger
command
R/Ctrl
pulseConfig PulseConfig CF R
pulseConfig
.cmdQual
ENUMERATED 0 (pulse) R
pulseConfig.onDur INT32U 2 ms (actually one pass) R
pulseConfig
.offDur
INT32U 0 R
pulseConfig
.numPls
INT32U 1 R
ctlModel CtlModels CF HiZPHIZ1.FrcTrigger.ctlModel R/W/C
sboTimeout INT32U CF 30000 R
sboClass SboClasses CF 0 (operate-once) R
LNName: HiZPHIZ1 LDevice inst: Ctrl UR element: HI-Z function