EasyManua.ls Logo

GE b30 - Page 383

GE b30
532 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE 3-145
3
3.5.3.24 Thermal overload (ThmOvl)
This element is instantiated in the following products: B30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, N60, T35,
T60.
Table 3-161: Thermal overload data objects
3.5.3.25 Three pole autoreclose (Rec3p)
This element is instantiated in the following products: D30, F35, F60, L30.
Table 3-162: Three pole autoreclose data objects
cdcNs VISIBLE
STRING255
EX Name of the GE Multilin
namespace at the time of this
firmware release
R
cdcName VISIBLE
STRING255
EX GEORG R
InRef3 ORG SYNCHK# SYNC CLOSE setting. R
setSrcRef ObjectReference SP SYNCHK# SYNC CLOSE. reference to the data attribute to input R/C
R
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
R
LNName: ThmOvlPTTR# LDevice inst: Ctrl UR element: THERMAL OVERLOAD PROTECTION # element
data obj. data attribute Type FC UR Name Description R/W/C
Op ACT THERMAL PROT # OP operand R
general BOOLEAN ST THERMAL PROT # OP R
Str ACD THERMAL PROT # PKP operand R
general BOOLEAN ST THERMAL PROT # PKP R
dirGeneral ENUMERATED ST 0, the code for unknown. R
InRef2 ORG THERMAL PROT # RESET setting. R
setSrcRef ObjectReference SP THERMAL PROT # RESET reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
BlkRef1 ORG THERMAL PROT # BLOCK setting. R
setSrcRef ObjectReference SP THERMAL PROT # BLOCK. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: Rec3pRREC# LDevice inst: Ctrl UR element: Autoreclose element # functions
data obj. data attribute Type FC UR Name Description R/W/C
ShotCnt INS AUTORECLOSE# SHOT COUNT actual
value
R
stVal INT32 ST AUTORECLOSE# SHOT COUNT R
AutoRecSt ENS Autoreclosing status R
stVal ENUMERATED ST R
Ena1 SPS AR# ENABLED operand R
stVal BOOLEAN ST AR# ENABLED R
ArRip SPS AR# RIP operand R
stVal BOOLEAN ST AR# RIP R
ArLO SPS AR# LO operand R
stVal BOOLEAN ST AR# LO R
ArBlk1 SPS AR# BLK FROM MAN CLS operand R
stVal BOOLEAN ST AR# BLK FROM MAN CLS R
OpCls ACT AR# CLOSE operand R
LNName: SynChkRSYN# LDevice inst: Ctrl UR element: Synchrocheck element # (ANSI 25)
data obj. data attribute Type FC UR Name Description R/W/C

Table of Contents