CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE 3-155
3
pulseConfig
   .numPls
INT32U 1 R
ctlModel CtlModels CF XCBR# Pos ctlModel R/W/C
sboTimeout INT32U CF XCBR# Pos sboTimeout R/W/C
sboClass SboClasses CF 0 (operate-once) R
operTimeout INT32U CF BREAKER # Toperate R/C
BlkOpn SPC Blocks breaker open commands  from all 
sources including protection
R/Ctrl
stVal BOOLEAN ST R
pulseConfig PulseConfig CF R
pulseConfig
   .cmdQual
ENUMERATED 1 (persistent) R
pulseConfig.onDur INT32U 0 R
pulseConfig
   .offDur
INT32U 0 R
pulseConfig
   .numPls
INT32U 0 R
ctlModel CtlModels CF XCBR# BlkOpn ctlModel R/W/C
sboTimeout INT32U CF 30000 R
sboClass SboClasses CF 0 (operate-once) R
operTimeout INT32U CF 0 R
BlkCls SPC Blocks breaker close commands from all 
sources
R/Ctrl
stVal BOOLEAN ST R
pulseConfig PulseConfig CF R
pulseConfig
   .cmdQual
ENUMERATED 1 (persistent) R
pulseConfig.onDur INT32U 0 R
pulseConfig
   .offDur
INT32U 0 R
pulseConfig
   .numPls
INT32U 0 R
ctlModel CtlModels CF XCBR# BlkCls ctlModel R/W/C
sboTimeout INT32U CF 30000 R
sboClass SboClasses CF 0 (operate-once) R
operTimeout INT32U CF 0 R
InRef1 ORG BREAKER # OPEN setting. R
GEORG R
setSrcRef ObjectReference SP BREAKER # OPEN reference to the data attribute to input R/C
VISIBLE 
STRING255
SP Reference to the ultimate source 
of value selected by setting 
BREAKER # OPEN
R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
VISIBLE 
STRING255
SP If reference is external to this 
IED, mapped to the source’s 
GOOSE control block, else empty 
string
R/C
cdcNs VISIBLE 
STRING255
EX Name of the GE Multilin 
namespace at the time of this 
firmware release
R
cdcName VISIBLE 
STRING255
EX GEORG R
InRef2 ORG BREAKER # BLK OPEN setting. R
GEORG R
setSrcRef ObjectReference SP BREAKER # BLK OPEN reference to the data attribute to input R/C
VISIBLE 
STRING255
SP Reference to the ultimate source 
of value selected by setting 
BREAKER # BLK OPEN
R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: Bkr0XCBR# LDevice inst: System UR element: Breaker Control element #
data obj. data attribute Type FC UR Name Description R/W/C