3.5.4.18 Transducer DCmA outputs (TDCOut)
This element is instantiated in the following products: B30, C30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60,
N60, T35, T60.
Table 3-191: DCmA output data objects
3.5.4.19 Transducer resistance temperature detectors (TRTDs)
This element is instantiated in the following products: G60, M60.
LNName: TDCOutGGIO1 LDevice inst: System UR element: DCmA outputs
data obj. data attribute Type FC UR Name Description R/W/C
Mod INC This logical node’s mode R/Ctrl
stVal ENUMERATED ST 1 (on) R
ctlModel CtlModels CF 0 (status only) R
Health INS This logical node’s health R
stVal ENUMERATED ST LPHD1.PhyHealth.stVal R
InRefΘ ORG DCMA OUTPUT φ SOURCE setting. R
GEORG R
setSrcRef ObjectReference SP Reference to the data object
selected by DCMA OUTPUT φ
SOURCE
reference to the data attribute to input R/C
VISIBLE
STRING255
SP Reference to the data object
selected by DCMA OUTPUT φ
SOURCE
R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
VISIBLE
STRING255
SP If reference is external to this
IED, mapped to the source’s
GOOSE control block, else empty
string
R/C
cdcNs VISIBLE
STRING255
EX Name of the GE Multilin
namespace at the time of this
firmware release
R
cdcName VISIBLE
STRING255
EX GEORG R
MaxValΘ ASG Maximum Value in deadband
calculations
R
setMag AnalogueValue SP R
setMag.f FLOAT32 “DCMA OUTPUT φ MAX VALUE” R/C
minVal AnalogueValue CF R
minVal.f FLOAT32 –90.000 R
maxVal AnalogueValue CF R
maxVal.f FLOAT32 90.000 R
stepSize AnalogueValue CF R
stepSize.f FLOAT32 0.001 R
MinValΘ ASG Minimum Value in deadband calculationsR
setMag AnalogueValue SP R
setMag.f FLOAT32 “DCMA OUTPUT φ MIN VALUE” R/C
minVal AnalogueValue CF R
minVal.f FLOAT32 –90.000 R
maxVal AnalogueValue CF R
maxVal.f FLOAT32 90.000 R
stepSize AnalogueValue CF R
stepSize.f FLOAT32 0.001 R