CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE 3-173
3
3.5.5.2 AC signal sources (ACsrc)
This element is instantiated in the following products: B30, C30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60,
N60, T35, T60.
Table 3-194: AC signal sources data objects
setSrcRef ObjectReference SP For communications, mapped to
Master ldName if not empty,
otherwise to the concatenation
of the IED name and “Master”.
For SCL, mapped to the
concatenation of the IED name
and “Master”.
reference to the data attribute to input R
MltLev SPG Instantiated only in the Master logical
device
R
setVal BOOLEAN SP R
<TTΣDataS
et##>
DATA-SET R
DSMemberRef[η] ObjectReference DataSet Member η R/C
LNName: ACsrcMMXU# LDevice inst: Meter UR element: AC Source #
data obj. data attribute Type FC UR Name Description R/W/C
Str ACD SRC# 50DD operand, which becomes On
when a disturbance (change in
magnitude of a sequence current greater
than twice the current cutoff level) is
detected on AC Source #.
R
general BOOLEAN ST SRC# 50DD R
dirGeneral ENUMERATED ST 0, the code for unknown R
TotW MV SRC # Three Phase Real Power, in primary
watts
R
instMag AnalogueValue MX R
instMag.f FLOAT32 SRC # Three Phase Real Power R
mag AnalogueValue MX R
mag.f FLOAT32 instMag.f deadbanded R
units Unit CF R
units.SIUnit ENUMERATED 38, the code for primary watts (J/s) R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
db INT32U CF MMXU# TotW DEADBAND R/W/C
zeroDb INT32U CF power cut-off level. R
TotVAr MV SRC # Three Phase Reactive Power, in
primary VAr
R
instMag AnalogueValue MX R
instMag.f FLOAT32 SRC # Three Phase Reactive
Power
R
mag AnalogueValue MX R
mag.f FLOAT32 instMag.f deadbanded R
units Unit CF R
units.SIUnit ENUMERATED 63, the code for primary volt amperes
reactive (VIsinΘ)
R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
db INT32U CF MMXU# TotVAr DEADBAND R/W/C
zeroDb INT32U CF power cut-off level. R
TotVA MV SRC # Three Phase Apparent Power, in
primary VA
R
instMag AnalogueValue MX R
instMag.f FLOAT32 SRC # Three Phase Apparent
Power
R
LNName: LLN0 LDevice inst: Meter UR element: Nameplate information for the logical nodes
data obj. data attribute Type FC UR Name Description R/W/C