EasyManua.ls Logo

GE b30 - Page 416

GE b30
532 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3-178 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
phsA.cVal.ang.f FLOAT32 instCVal.ang.f deadbanded R
phsA.units Unit CF R
phsA.units.SIUnit ENUMERATED 5, the code for primary amperes R
phsA.units
.multiplier
ENUMERATED 0, the code for a multiplier of 1 R
phsA.db INT32U CF MMXU# A.phsA .db R/W/C
phsA.dbAng INT32U CF MMXU# A.phsA.dbAng R/W/C
phsA.zeroDb INT32U CF current cut-off level. R
phsB CMV R
phsB.instCVal Vector MX R
phsB.instCVal.mag
.f
FLOAT32 SRC # Phase B Current
Magnitude
R
phsB.instCVal.ang
.f
FLOAT32 SRC # Phase B Current Angle UR range -180...+180 converted to 0...360R
phsB.cVal Vector MX R
phsB.cVal.mag.f FLOAT32 instCVal.mag.f deadbanded R
phsB.cVal.ang.f FLOAT32 instCVal.ang.f deadbanded R
phsB.units Unit CF R
phsB.units.SIUnit ENUMERATED 5, the code for primary amperes R
phsB.units
.multiplier
ENUMERATED 0, the code for a multiplier of 1 R
phsB.db INT32U CF MMXU# A.phsB.db R/W/C
phsB.dbAng INT32U CF MMXU# A.phsB.dbAng R/W/C
phsB.zeroDb INT32U CF current cut-off level. R
phsC CMV R
phsC.instCVal Vector MX R
phsC.instCVal.mag
.f
FLOAT32 SRC # Phase C Current
Magnitude
R
phsC.instCVal.ang
.f
FLOAT32 SRC # Phase C Current Angle UR range -180...+180 converted to 0...360R
phsC.cVal Vector MX R
phsC.cVal.mag.f FLOAT32 instCVal.mag.f deadbanded R
phsC.cVal.ang.f FLOAT32 instCVal.ang.f deadbanded R
phsC.units Unit CF R
phsC.units.SIUnit ENUMERATED 5, the code for primary amperes R
phsC.units
.multiplier
ENUMERATED 0, the code for a multiplier of 1 R
phsC.db INT32U CF MMXU# A.phsC.db R/W/C
phsC.dbAng INT32U CF MMXU# A.phsC.dbAng R/W/C
phsC.zeroDb INT32U CF current cut-off level. R
res CMV R
res.instCVal Vector MX R
res.instCVal.mag
.f
FLOAT32 SRC # Neutral Current
Magnitude
R
res.instCVal.ang
.f
FLOAT32 SRC # Neutral Current Angle UR range -180...+180 converted to 0...360R
res.cVal Vector MX R
res.cVal.mag.f FLOAT32 instCVal.mag.f deadbanded R
res.cVal.ang.f FLOAT32 instCVal.ang.f deadbanded R
res.units Unit CF R
res.units.SIUnit ENUMERATED 5, the code for primary amperes R
res.units
.multiplier
ENUMERATED 0, the code for a multiplier of 1 R
res.db INT32U CF MMXU# A.neut.db R/W/C
res.dbAng INT32U CF MMXU# A.neut.dbAng R/W/C
LNName: ACsrcMMXU# LDevice inst: Meter UR element: AC Source #
data obj. data attribute Type FC UR Name Description R/W/C

Table of Contents

Other manuals for GE b30

Related product manuals