3-180 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
cVal Vector MX R
cVal.mag.f FLOAT32 instCVal.mag.f deadbanded R
cVal.ang.f FLOAT32 instCVal.ang.f deadbanded R
units Unit CF R
units.SIUnit ENUMERATED 5, the code for primary amperes R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
db INT32U CF MMXU# Dif Gnd Cur.db R/W/C
dbAng INT32U CF MMXU# Dif Gnd Cur.dbAng R/W/C
zeroDb INT32U CF current cut-off level. R
angRef ENUMERATED CF See UR product manual regarding
FREQUENCY AND PHASE REFERENCE
R
W WYE SRC # Phase Real Power, in primary wattsR
phsA CMV R
phsA.instCVal Vector MX R
phsA.instCVal.mag
.f
FLOAT32 SRC # Phase A Real Power R
phsA.cVal Vector MX R
phsA.cVal.mag.f FLOAT32 instCVal.mag.f deadbanded R
phsA.units Unit CF R
phsA.units.SIUnit ENUMERATED 38, the code for primary watts (J/s) R
phsA.units
.multiplier
ENUMERATED 0, the code for a multiplier of 1 R
phsA.db INT32U CF MMXU# W.phsA DEADBAND R/W/C
phsA.zeroDb INT32U CF power cut-off level. R
phsB CMV R
phsB.instCVal Vector MX R
phsB.instCVal.mag
.f
FLOAT32 SRC # Phase B Real Power R
phsB.cVal Vector MX R
phsB.cVal.mag.f FLOAT32 instCVal.mag.f deadbanded R
phsB.units Unit CF R
phsB.units.SIUnit ENUMERATED 38, the code for primary watts (J/s) R
phsB.units
.multiplier
ENUMERATED 0, the code for a multiplier of 1 R
phsB.db INT32U CF MMXU# W.phsB DEADBAND R/W/C
phsB.zeroDb INT32U CF power cut-off level. R
phsC CMV R
phsC.instCVal Vector MX R
phsC.instCVal.mag
.f
FLOAT32 SRC # Phase C Real Power R
phsC.cVal Vector MX R
phsC.cVal.mag.f FLOAT32 instCVal.mag.f deadbanded R
phsC.units Unit CF R
phsC.units.SIUnit ENUMERATED 38, the code for primary watts (J/s) R
phsC.units
.multiplier
ENUMERATED 0, the code for a multiplier of 1 R
phsC.db INT32U CF MMXU# W.phsC DEADBAND R/W/C
phsC.zeroDb INT32U CF power cut-off level. R
VAr WYE SRC # Phase Reactive Power, in primary
VAr
R
phsA CMV R
phsA.instCVal Vector MX R
phsA.instCVal.mag
.f
FLOAT32 SRC # Phase A Reactive Power R
phsA.cVal Vector MX R
LNName: ACsrcMMXU# LDevice inst: Meter UR element: AC Source #
data obj. data attribute Type FC UR Name Description R/W/C