Section 4 - Maintenance & Troubleshooting
37
Problem Possible Solution
E3 error is displayed on
LCD (NOT OK Condition
detected).
Verify that connectors are firmly seated and
free of corrosion
Verify transducer is properly wired
Verify no shorts exist between wires at connector
Verify that the transducer power supply is working
properly by measuring the voltage between
transducer PWR(RED)and COM(BLK). Acceptable
range is 4.9 to 5.2 Vdc
Verify that the transducer cable is working
properly by replacing it with a known good cable
Verify that the transducer is working properly by
either replacing it with a known good transducer or
by testing the existing transducer for proper
operation on a shake table.