Group Value Displayed Failure Code Definition Setting Criteria
Defrost
200 thru 299
F200 0 2 0 0
FZ Defrost Heater on for Max Time.
Any time the FZ Defrost Turns off based on Time
F201 0 2 0 1
FF Defrost Heater on for Max Time.
Any Time the FF defrost turns off based on Time
F202 0 2 0 2
5 consecutive FZ abnormal defrosts.
5 consecutive abnormal defrosts.
F203 0 2 0 3
5 consecutive FF abnormal defrosts.
5 consecutive abnormal defrosts.
FZ Evap.
Thermistor
OPEN or short FZ Evaporator Thermistor:
This will impact defrost only as follows:
1. All FZ heater defrosts will be 20 minutes.
2. The FZ abnormal defrost flag will also be set.
FF Evap.
Thermistor
OPEN or short FZ Evaporator Thermistor:
This will impact FF defrost only as follows:
1. All FF heater defrost will be 20 minutes.
2. The FF abnormal defrost flag will also be set.
Defrost Failure Codes