9.3 Operating Environment
Temperature Humidity Altitude Storage temperature
0°C~40°C
<95% <1000m
-15°C~40°C
Note: Output power is derated when UPS is above 1000m as following:
Altitude (M) 1000
1500
2000
2500
3000
3500
4000
4500
5000
Derating Power
100%
95% 91% 86% 82% 78% 74% 70% 67%