-17-
10. INSTALLATION - EP6000
10.1 Unpacking and Inspection
1) Unpack the packaging and check the package contents. The shipping package
contains:
l An UPS
l An user manual
l A communication cable (RS232)
l A communication cable (USB)
l A Software CD
l SNMP card (optional)
l Battery cable (long backup time model battery pack only)
2) Inspect the appearance of the UPS to see if there is any damage during
transportation. Do not turn on the unit and notify the carrier and seller
immediately if there is any damage or lacking of some parts.
10.2 Input and output power cords and protective earth ground installation
1. Notes for installation
1) The UPS must be installed in a location with good ventilation, far away from
water, inflammable gas and corrosive agents.
2) Ensure the air vents on the front and rear of the UPS are not blocked. Allow at
least 0.5m of space on each side.
3) Condensation may occur if the UPS is unpacked in a very low temperature
environment. In this case it is necessary to wait until the UPS is fully dried
inside before proceeding installation and use. Otherwise there are hazards of
electric shock.
2. Installation
Installation and wiring must be performed in accordance with the local electric
code and the following instructions by professional person.
For safety, please cut off the mains power switch before installation.The battery
breaker also needs to be cut off if it is a long backup time model (“LRT” model)
or Rack model (“R” model).
1) Open the terminal block cover located on the rear panel of the UPS, please
refer to the appearance diagram.
2) It is recommended to select the UL1015 10AWG(6mm
2
) wire or other
insulated wire which complies with AWG Standard for the UPS input and