-18-
output wirings.
Note: Do not use the wall receptacle as the input power source for the UPS, as its
rated current is less than the UPS’s maximum input current. Otherwise the
receptacle may be burned and destroyed.
3) Connect the input and output wires to the corresponding input and output
terminals according to the following diagram.
Note: you must make sure that the input and output wires and the input and
output terminals are connected tightly.
4) It is recommended to select the UL1015 10AWG(6mm
2
) green wire with
yellow ribbon for protective earth ground wire.
5) After having completed the installation, make sure the wiring is correct.
6) Please install the leak current protective breaker at the output power
distribution panel of the UPS if necessary.
7) To connect the load with the UPS, please turn off all the loads first, then
perform the connection and finally turn on the loads one by one.
8) No matter the UPS is connected to the utility power or not, the output of the
UPS may have electricity. The parts inside the unit may still have hazardous
voltage after turning off the UPS. To make the UPS have no output, power off
the UPS, and then disconnect the utility power supply.
9) Suggest charging the batteries for 8 hours before use. After connection, turn
the input breaker in the “ON” position, the UPS will charge the batteries
automatically. You can also use the UPS immediately without charging the
batteries first, but the backup time may be less than the standard value.
10) If it is necessary to connect the inductance load such as a monitor or a laser
printer to the UPS, the start-up power should be used for calculating the capacity
of the UPS, as its start-up power consumption is too big when it is started.
Input and output Terminal Block wiring diagram of EP6000