-29-
Appendix 1: Corresponding Form of the LED Display
- EP700/1000/2000/3000
LED display
No.
Operating state
#
1
#
2
#
3
#
4
#
5
#
6
#
7
#
8
#
9
#
10
Alarm warning
1
0~30%
Load capacity
none
2
31%~50%
Load capacity
none
3
51%~70%
Load capacity
none
4
71%~95%
Load capacity
none
5
Utility
Power
Mode
96%~108%
Load capacity
none
6
0~25%
Battery capacity
Beep once every sec
7
26%~50%
Battery capacity
Beep once every 4 sec
8
51%~75%
Battery capacity
Beep once every 4 sec
9
76%~100%
Battery capacity
Beep once every 4 sec
10
Battery
Mode
100%
Battery capacity
Beep once every 4 sec
11
Bypass mode
Beep once every 2 min.
12
overloaded in utility mode and
UPS still in INV mode
Beep twice every sec.
13
overloaded in utility mode and
UPS in bypass mode
Continuously beep
14
Utility power abnormal
15
Overloaded in battery mode,
Early-warning
Beep twice every sec.
16
Overloaded in battery mode,
Cut off the output
Continuously beep
17
Over temperature
Continuously beep
18
Inv abnormal
Continuously beep
19
Output short circuited
Continuously beep
20
BUS voltage abnormal
Continuously beep
21
Charger voltage too high
Continuously beep
22
Fan abnormal
Beep once every sec
23
Charge or battery failed
Beep once every sec
24
Battery voltage abnormal
25
Site Fault
Beep once every 2 min.
: Solid ON : Flash :LED display and alarm warning are dependent on other conditions.