EasyManua.ls Logo

GE EP 700T - Appendix 2: Corresponding Form of the LED Display - EP6000

GE EP 700T
119 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
-30-
Appendix 2: Corresponding Form of the LED Display
- EP6000
LED display
No
Operating state
#
1
#
2
#
3
#
4
#
5
#
6
#
7
#
8
#
9
#
10
Alarm warning
1
0~35%
Load capacity
none
2
36%~55%
Load capacity
none
3
56%~75%
Load capacity
none
4
76%~95%
Load capacity
none
5
Utility
Power
Mode
96%~105%
Load capacity
none
6
0~20%
Battery capacity
Beep once every sec
7
21%~40%
Battery capacity
Beep once every 4 sec
8
41%~60%
Battery capacity
Beep once every 4 sec
9
61%~80%
Battery capacity
Beep once every 4 sec
10
Battery
Mode
81%~100%
Battery capacity
Beep once every 4 sec
11
Bypass mode
Beep once every 2
min.
12
overloaded in utility mode and
UPS still in INV mode
Beep twice every sec.
13
overloaded in utility mode and
UPS in bypass mode
Beep twice every sec.
14
Utility power abnormal
15
Overloaded in battery mode,
Early-warning
Beep twice every sec.
16
Overloaded in battery mode,
Cut off the output
Continuously beep
17
Over temperature
Continuously beep
18
Inv abnormal
Continuously beep
19
Output short circuited
Continuously beep
20
BUS voltage abnormal
Continuously beep
21
Charger and battery failed
Beep once every sec
22
BAT SCR failed
Continuously beep
23
Fan abnormal
Beep once every sec
24
INV RLY failed
Continuously beep
25
Communication abnormal
Continuously beep
: Solid ON : Flash :LED display and alarm warning are dependent on other conditions.