19
FVR-C9S-2UX
Terminal Function Explanation
Classi-
fication
Terminal Code Terminal Name Explanation of Function
Output for
Motor
FM Analog Monitor
Outputs + 10VDC between FM and CM terminals. When
frquency setting is equal to the maximum frequency setting,
outputs + 10VDC at 150% current when monitoring output
current.
• Two DC voltmeters (internal resistance of 10K ohm or
greater) can be connected.
• In case of DC ammeter (1mA full scale), it is necessary to
add series resistance of 10K ohm (1/2W)
• This output is a pulse output constant frequency (38. 1 Hz)
which has a variable duty.
Contact
Output
30A, B, C
Combined Alarm Output
Terminals
Output via no volt signal (contact1c) to indicate that the
drive's protective function has been activated by an alarm.
• Contact capacity (DC48V. 0.3A)
C92-04