Kilsen KFP-CF Series Operation Manual 9
Out of service
WARNING: When the control panel indicates Out of Service, your fire alarm system is
inactive and your site is not protected. Contact your installation or maintenance
contractor immediately to investigate the problem.
The control panel is out of service when there is insufficient or no mains and/or
battery power. In this state there is no further fire alarm or fault warning and all panel
operation stops.
Out of service is indicated as follows:
The Supply LED flashes if there is no mains power and the battery voltage is
insufficient.
The Supply LED is steady if the mains power is insufficient and no battery power is
detected.
The Out of Service LED is steady.
The internal buzzer sounds intermittently.
When power is re-established the control panel returns to its former status.
Caution: To avoid damage to batteries, we recommended that you disconnect them
when the control panel is out of service.