This is the pick-up current for earth fault protection. It is set as a fraction of the
breakers rating (Ir). Switch positions are provided at OFF, 0.4In, 0.6In, 0.8In and
1.0In. The OFF position disables earth fault protection.
3.6 Ear3.6 Ear
3.6 Ear3.6 Ear
3.6 Ear
th Fth F
th Fth F
th F
ault Delay - OPTIONALault Delay - OPTIONAL
ault Delay - OPTIONALault Delay - OPTIONAL
ault Delay - OPTIONAL
The fixed-time earth-fault delay can be set to instantaneous, 0.1s 0.2s, 0.4s, 0.6s,
0.8s or 1.0s
3.5 Er3.5 Er
3.5 Er3.5 Er
3.5 Er
dschlusschutz-Ansprdschlusschutz-Anspr
dschlusschutz-Ansprdschlusschutz-Anspr
dschlusschutz-Anspr
echwechw
echwechw
echw
erer
erer
er
t (Ift (If
t (Ift (If
t (If
) - Optional) - Optional
) - Optional) - Optional
) - Optional
Der Erdschlussschutz-Ansprechwert ist einstellbar als Vielfaches des Stromes In.
Mögliche Einstellungen sind AUS, 0,4x In, 0,6x In, 0,8x In und 1,0x In. In der Stellung
OFF ist dieser Schutz deaktiviert.
3.6 Er3.6 Er
3.6 Er3.6 Er
3.6 Er
dschlussschutz-Zeitvdschlussschutz-Zeitv
dschlussschutz-Zeitvdschlussschutz-Zeitv
dschlussschutz-Zeitv
erer
erer
er
zögerzöger
zögerzöger
zöger
ung - Optionalung - Optional
ung - Optionalung - Optional
ung - Optional
Die vorgegebene Erdschlussschutz – Zeitverzögerung kann eingestellt werden
zwischen INST (unverzögert), 0,1s, 0,2s, 0,4s, 0,6s, 0,8s und 1s.
Strom xln
Strom xln
3.4 Instantaneous pr3.4 Instantaneous pr
3.4 Instantaneous pr3.4 Instantaneous pr
3.4 Instantaneous pr
otectionotection
otectionotection
otection
• The instantaneous-protection function protects the distribution system against
solid short-circuits. Contrary to the short-time protection function, the tripping
delay for instantaneous protection is not adjustable.
• The trip signal is sent to the circuit breaker as soon as current exceeds the set
value. This function is based on peak measurements.
• User can choose the instantaneous pickup as OFF, 2, 3, 4, 6, 8, 10. For OFF
setting instantaneous will be disabled.
Note: - It is recommended not to turn Inst OFF
3.43.4
3.43.4
3.4
UnvUnv
UnvUnv
Unv
erer
erer
er
zögerzöger
zögerzöger
zöger
ter Kter K
ter Kter K
ter K
urur
urur
ur
zschlussschutzzschlussschutz
zschlussschutzzschlussschutz
zschlussschutz
Der Unverzögerte Kurzschluss Kanal schützt die Verteilung gegen hohe
Kurzschlussströme. Im Gegensatz zum Kurzeitschutz ist die Auslöseverzöger ung
für den Kurzschlussschutz nicht einstellbar.
Der Auslöseimpuls wird sofort , bei überschreiten eines Grenzwertes erzeugt.
Diese Messung basiert auf einer Spitzenstrommessung.
Die Grenzwerte können eingestellt werden zu: Aus (OFF), 2, 3, 4, 5, 8, 10. In
Stellung Aus ist der Kanal abgeschaltet. Es ist empfohlen diesen Kanal nicht
abzuschalten.
IN S T
Strom xln
OPERATOR
CONTROL