RECOMMENDED
MAINTENANCE
FOR
MAONE
-
EIAST
BREAKERS
APPLIED
TO
REPETITIVE
SWITCHING
DUTY
;
~
~
—
-
•
s
.
'
I
.
Magne
-
blasfe
breakers
applied
to
repetitive
switching
duty
should
be
serviced
and
maintained
according
to
the
following
schedule
;
A
.
Every
500
Operations
*
or
Every
Six
Months
-
Whichever
Comes
First
1
.
Remove
the
rear
*
side
,
and
inter
phase
barriers
.
2
o
Wipe
all
insulating
parts
clean
of
smoke
deposit
-
and
dust
with
a
clean
dry
cloth
,
including
the
bushings
,
and
the
inside
of
the
barriers
.
I
3
.
All
parts
in
the
throat
area
of
the
arc
chute
should
be
thorough
-
ly
cleaned
by
using
sandpaper
.
This
cleaning
should
be
perform
-
ed
any
time
the
arc
chute
is
removed
.
The
arc
chute
fins
should
not
be
cleaned
.
Whenever
the
arc
chute
is
removed
,
loose
dust
and
dirt
should
be
blown
out
before
replacing
arc
chutes
.
B
.
Every
1000
Operations
,
or
Every
Six
Months
-
Whichever
Comes
First
1
.
In
addition
to
the
servicing
done
each
500
operations
,
the
breaker
contacts
,
breaker
adjustments
,
and
mechanism
adjust
-
ments
should
be
checked
.
2
.
Primary
Contacts
-
Inspect
the
condition
of
the
stationary
con
-
tact
fingers
and
movable
contact
blocks
.
Badly
pitted
or
burn
-
ed
contacts
should
be
replaced
.
(
Note
:
burned
primary
contacts
indicate
the
probable
need
for
arcing
contact
replacement
.
)
If
the
contact
surfaces
are
only
roughened
or
galled
,
they
should
be
smoothed
with
crocus
cloth
or
draw
filed
.
After
contact
dressing
the
contacts
should
be
greased
with
a
-
very
thin
film
of
G
.
E
.
contact
lubricant
D
50
H
47
.
3
.
Arcing
Contacts
-
When
the
arcing
contact
wipe
is
less
than
the
minimum
specified
under
ADJUSTMENTS
,
page
6
,
the
contacts
should
be
replaced
.
The
contacts
should
be
Inspected
for
uneven
wear
and
/
or
damage
using
a
mirror
to
inspect
the
stationary
contacts
.
Normally
it
will
not
be
necessary
to
remove
the
arc
chutes
for
this
1000
operation
servicing
unless
inadequate
wipe
or
contact
conditions
indicate
a
need
for
replacement
.
If
the
arc
chutes
are
removed
,
the
contact
braids
and
other
parts
subject
to
arc
-
ing
should
be
checked
for
possible
cleaning
or
replacement
.
Do
not
grease
the
arcing
contacts
under
any
circumstances
.
4
.
Check
the
breaker
and
mechanism
adjustments
as
summarised
under
INSPECTION
AND
TEST
,
page
10
.
The
necessary
readjustments
should
be
made
as
described
under
ADJUSTMENTS
,
page
6
.
I
I
17
Courtesy of NationalSwitchgear.com