GEI
-
88766
TRIP
COIL
To
replace
the
potential
trip
coil
(
2
)
*
Fig
.
11
proceed
as
follows
1
1
.
With
the
breaker
in
the
open
position
*
remove
the
two
mounting
bolts
(
3
)
.
2
.
Remove
upper
support
(
l
)
and
spacers
.
3
.
Cut
wires
at
the
butt
connectors
and
remove
coil
.
4
.
When
replacing
the
coil
be
sure
to
assemble
the
correct
fiber
spa
-
cers
at
the
ends
before
bolting
support
(
l
)
.
5
.
Adjust
coil
location
to
allow
approximately
1
/
4
"
of
armature
travel
before
latch
starts
to
move
.
i
b
.
Butt
connect
wires
and
check
operation
of
solenoid
electrically
and
mechanically
.
SPRING
RELEASE
COIL
To
remove
the
spring
release
coil
(
5
)
Fig
.
6
proceed
as
follows
;
1
.
Block
the
closing
springs
as
described
in
INSTALLATION
,
«
2
.
Remove
the
left
hand
closing
spring
as
described
in
.
CLOSING
SPRINGS
below
.
3
.
Remove
two
mounting
bolts
(
17
)
,
coil
support
(
l
8
)
,
and
spacers
.
4
.
Cut
wires
at
the
butt
connectors
and
remove
coil
.
5
.
Replace
the
coil
and
the
correct
number
of
fiber
spacers
before
bolt
-
ing
support
.
6
.
Butt
connect
wires
and
check
that
the
armature
is
not
binding
,
coil
for
electrical
operation
.
Check
CLOSING
SPRINGS
I
The
closing
springs
(
6
)
Fig
.
3
can
be
removed
as
follows
;
1
.
Charge
the
springs
with
the
"
manual
charging
wrench
and
apply
the
spring
blocking
device
as
described
in
INSTALLATION
.
2
*
Discharge
springs
by
pushing
manual
close
button
(
7
)
Fig
.
2
.
#
28
Courtesy of NationalSwitchgear.com