P40 Agile P14D, P14N, P94V Version History
P40Agile-VH-EN-9 5
Major Minor
Relay type: Agile P14N, P14D and P94V
Software
Version
Hardware
Suffix
Original Date of
Issue
Description of Changes Technical Documentation
· Add P14DH variant with Wattmetric Directional Earthfault protection
The .lng files generated by building and the .LNG files used by S1 Agile are inconsistent.
Incorrect russian translations for DDB_CONTROL_TRIP & DDB_CONTROL_CLOSE
P14DH 53A IEC61850-8-1 Level B Conformance Failure/Issue
Inconsistent language text strings between P40Agile and P14x.
B A Apr-14
CB Fail trip may fail to operate under faults with DC transient offsets
· Integrate new FPGA version to fix transistor issue
C A Apr-15
Agile Relay failure: Error/Lockout 7104:2000/reboot
The LCD display year is 2080 but in the disturbance and event records it is 1980.
Using S1 Agile changing values to the Voltage Transformer does not change the corresponding vaues in Residual
O/V NVD column
Line length mismatch between value sent from S1 Agile and the value received in the relay
DNP3oE Setting Files - GoEna is visible
Values under High impedance menu do not show values in primary when relay is set to primary in S1.
53 D A Aug-2015
Very sharp pick current level lead relay tripping on IREF
53 E A April-2017
IEC 61850 - Connection / Disconnection issues
DNP3oE Versions - Courier Tunnelling doesnot work
DNPOE after operated some DI and AI events at the same time ,the relay Ethernet board seems locked and after a
while the relay reboot.
DNP Over Ethernet Application Crash after many days of Polling
Permanent ethernet communication loss in P40 Agile relays
TCP disrupts after around 206 days of continuous use
P14DZ HiZ Function asserting incorrectly (CHA HiF)
Incorrect Burst Count - HiF Detection
FA Steady Fault - Incorrect Assertion
HIF CHA Hysteresis is not correctly set
HIF Burst Threshold is not reset after the adaptive threshold is disabled
Maintenance Record Generated Everytime Gateway is configured in DNP configuration
CS1 and CS2 does not work independently whey CB Comp enabled for CS2
New opto threshold for Russian requirement
New reduced I/O option (3I/4O in 20TE and 6I/8O in 30TE)
IEC 61850 Client disassociation while reading PloGGIO1$CO block in P14D IEDs
IEC 61850: incorrect Courier cell mapping to TotWh and TotVArh in MMTR LNs
IEC61850 measurements negative values rounding error
54 A
P14D-TM-EN-3
P14N-TM-EN-3
P94V-TM-EN-3
A A Apr-14
53
P14D-TM-EN-3
P14N-TM-EN-3
P94V-TM-EN-3
P14D-TM-EN-4.1
P14N-TM-EN-4.1
P94V-TM-EN-4.1
Dec-14A

Questions and Answers: