Micro
Versa
Trip
®
Plus
and
Micro
Versa
Trip
®
PM
Trip
Units
Chapter
2
.
Setup
Mode
m
Potential
Transformer
Primary
Voltage
Enter
the
primary
voltage
rating
of
the
potential
Note
that
this
step
applies
only
to
MicroVersaTrip
transformer
,
as
illustrated
in
Figure
34
.
The
range
of
PM
trip
units
connected
to
either
POWER
LEADER
values
is
120
to
600
volts
,
with
an
increment
of
1
volt
,
or
Epic
MicroVersaTrip
systems
.
With
POWER
LEADER
systems
the
address
is
assigned
at
the
breaker
.
The
set
point
values
are
sep
-
arated
by
decimal
points
to
differentiate
the
addresses
from
other
set
points
,
as
illustrated
in
Figure
36
.
The
address
options
are
from
256
to
999
.
Communication
Address
CAUTION
:
Incorrect
storage
of
this
set
point
will
result
in
incorrect
metering
values
.
Even
if
this
set
-
ting
is
entered
remotely
,
it
must
be
entered
again
locally
.
SETUP
VOLTS
SETUP
E
.
5
.
E
Ell
Figure
36
.
Trip
unit
display
for
setting
communication
address
.
Figure
34
.
Trip
unit
display
for
potential
transformer
primary
voltage
setpoint
.
With
Epic
MicroVersaTrip
systems
,
the
Epic
system
s
Field
Programming
Unit
(
FPU
)
calls
for
removal
of
the
rating
plug
.
This
is
not
required
for
addressing
a
MicroVersaTrip
PM
trip
unit
.
Simply
press
ENTER
to
identify
the
unit
to
the
FPU
.
The
address
shown
on
the
FPU
s
display
must
not
be
changed
at
the
breaker
.
Potential
Transformer
Connection
Note
that
this
step
applies
only
to
MicroVersaTrip
PM
trip
units
.
Select
the
appropriate
potential
transformer
connec
-
tion
,
either
line
-
to
-
line
(
VL
-
L
)
or
line
-
to
-
neutral
(
VL
-
N
)
,
as
illustrated
in
Figure
35
.
CAUTION
:
Incorrect
storage
of
this
set
point
will
result
in
incorrect
metering
values
.
Even
if
this
set
-
ting
is
entered
remotely
,
it
must
be
entered
again
locally
,
VOLTS
SETUP
VL
-
L
Figure
35
.
Trip
unit
display
for
potential
transformer
connection
choice
.
:
?
>
v
.
'
'
A
.
19