GE MicroVersaTrip Plus - Rating Plug and Voltage Settings; Transformer Connection

GE MicroVersaTrip Plus
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Micro
Versa
Trip
®
Plus
and
Micro
Versa
Trip
®
PM
Trip
Units
Chapter
4
.
Status
Mode
When
the
set
point
is
reached
,
but
before
the
time
delay
has
expired
,
the
flashing
stops
,
indicating
that
4
-
1
Overview
Status
mode
is
the
normal
display
mode
for
breaker
trip
is
imminent
,
information
.
The
status
display
identifies
an
immi
-
nent
overcurrent
trip
,
then
,
afterward
,
target
displays
that
indicate
the
reason
for
the
trip
.
STATUS
Status
displays
reflect
the
options
ordered
with
the
trip
unit
.
All
MicroVersaTrip
Plus
and
MicroVersaTrip
PM
trip
units
provide
information
on
long
-
time
overcurrent
protection
.
Only
PM
style
trip
units
can
be
equipped
with
protective
relays
and
,
consequently
,
display
information
about
them
.
The
trip
unit
must
be
provided
with
control
power
to
display
status
information
.
This
can
come
from
a
MicroVersaTrip
Test
Kit
,
a
MicroVersaTrip
battery
pack
,
an
external
24
Vdc
power
supply
,
or
energizing
the
breaker
to
at
least
20
%
of
its
sensor
load
.
PICKUP
Figure
48
.
Trip
unit
status
display
for
long
-
time
overcurrent
pickup
.
When
the
breaker
trips
for
long
-
time
overcurrent
,
the
target
display
indicates
OVERLOAD
,
as
illustrated
in
Figure
49
.
STATUS
4
-
2
Status
Mode
Operation
OVERLOAD
This
section
describes
each
of
the
status
displays
and
the
sequences
in
which
they
appear
.
Figure
49
.
Trip
unit
status
display
for
long
-
time
overcurrent
trip
.
Normal
Status
Display
When
the
breaker
is
closed
and
its
circuit
energized
,
the
normal
status
display
appears
,
as
illustrated
in
Figure
47
.
This
display
indicates
that
the
trip
unit
i
not
in
long
-
time
pickup
.
Short
-
Time
Overcurrent
Target
Display
ls
After
a
short
-
time
trip
,
the
status
display
appears
as
in
Figure
50
.
The
display
does
not
flash
.
STATUS
STATUS
NORMAL
SHORT
CIRCUIT
Figure
47
.
Trip
unit
display
for
normal
status
.
Figure
50
.
Trip
unit
status
display
for
short
-
time
overcurrent
trip
.
Long
-
Time
Overcurrent
Pickup
and
Target
Displays
When
the
long
-
time
overcurrent
function
has
reached
95
%
of
the
trip
unit
s
current
rating
,
C
,
PICKUP
begins
to
flash
on
the
display
,
as
illustrated
in
Figure
48
.
During
the
transition
from
95
%
to
100
%
of
the
set
point
,
the
frequency
of
flashing
increases
.
Instantaneous
Target
Display
The
status
display
for
an
instantaneous
trip
is
similar
to
that
for
a
short
-
time
trip
,
as
in
Figure
50
,
except
that
SHORT
CIRCUIT
flashes
repeatedly
.
©
24
Courtesy of NationalSwitchgear.com