SECTION
4
INSTALLING
THE
CONVERSION
KIT
Front
and
Back
Frame
Reassembly
METAL
BREAKER
FRAMES
Step
1
.
Use
the
(
2
)
Me
-
18
xl
bolts
with
plain
and
lock
washers
provided
to
fasten
each
CT
assembly
to
the
contact
arms
on
the
front
frame
(
Fig
.
25
)
.
Tighten
the
bolts
to
100
in
.
lbs
.
*
Step
2
.
Carefully
reassemble
the
front
and
back
frames
.
Use
the
hardware
removed
in
steps
5
and
6
on
page
5
to
hold
the
frames
together
.
Step
3
.
Return
the
two
line
terminal
housings
and
fasten
in
place
with
the
hardware
removed
in
steps
3
and
4
on
page
4
(
Fig
.
26
)
.
Step
4
.
Return
the
draw
out
interlock
lever
removed
in
step
2
on
page
4
.
Step
5
.
Tighten
the
CT
bolts
inserted
in
step
3
on
page
10
to
200
in
.
lbs
.
*
(
Fig
.
27
)
.
Fig
.
25
.
CT
Assembly
Installation
*
IMPORTANT
NOTE
:
Steps
designated
by
an
(
*
)
are
critical
electrical
integrity
connec
-
tions
.
They
must
be
correctly
tightened
for
proper
operation
.
Failure
to
tighten
properly
will
cause
a
breaker
failure
resulting
in
prop
-
erty
damage
or
personal
injury
.
Fig
.
26
.
Frame
Assembly
Fig
.
27
.
CT
Bolt
Torque