Loading...
SECTION
4
INSTALLING
THE
CONVERSION
KIT
CROSSBAR
Flux
Shifter
/
Programmer
Bracket
Installation
(
Cont
d
)
SLATE
BREAKER
FRAMES
Step
4
.
Place
the
end
of
the
reset
link
with
the
!
4
"
hole
over
the
!
4
pin
on
the
end
of
the
cross
bar
(
Fig
.
40
)
.
The
notched
edge
is
up
.
Use
the
plain
washer
and
cotter
pin
provided
to
fasten
the
link
.
Step
5
.
The
slot
in
the
opposite
end
of
the
link
is
placed
over
the
bottom
stud
on
the
flux
shifter
reset
arm
Use
the
nut
and
washer
already
assembled
on
the
stud
to
hold
in
place
(
Fig
.
41
)
.
Step
6
.
Place
the
slotted
draw
out
interlock
link
removed
in
Step
2
on
page
6
over
the
two
posts
on
the
front
and
back
frames
.
Use
the
existing
washers
and
new
cotter
pins
provided
to
fasten
it
.
Step
7
.
Add
the
new
link
shown
in
(
Fig
.
42
)
by
threading
the
!
/
4
-
20
x
Vi
'
screw
through
the
%
"
bushing
pro
-
vided
with
the
link
.
Step
8
.
Bend
the
tang
on
the
trip
paddle
until
the
trip
bar
can
rotate
to
the
fully
reset
position
and
there
is
not
more
than
Vn
"
clearance
between
the
tang
and
the
new
interlock
link
(
Fig
.
42
)
.
Fig
.
40
.
Reset
Link
Installation
RESET
LINK
RESET
ARM
STUD
NEW
LINK
I
Fig
.
41
.
Reset
Arm
Assembly
OLD
LINK
S
'
r
Fig
.
42
.
Interlock
Linkage