SECTION
5
FOUR
-
WIRE
GROUND
FAULT
OPTION
INSTALLING
NEUTRAL
SENSORS
The
neutral
sensor
is
an
electrical
duplicate
of
the
phase
sensor
,
including
the
taps
.
Therefore
,
when
taps
(
if
provided
)
are
changed
on
the
phase
sen
-
sors
,
the
taps
on
the
neutral
sensor
must
be
corre
-
spondingly
positioned
.
For
kits
with
fixed
phase
sen
-
sors
,
be
sure
to
use
the
corresponding
tap
on
the
neutral
sensor
.
Mount
the
neutral
sensor
in
the
outgoing
neutral
lead
,
normally
in
the
equipment
s
bus
or
cable
com
-
partment
,
see
Fig
.
5
-
6
and
5
-
7
.
Pig
.
5
-
6
.
Outline
of
the
AK
-
75
,
AK
-
100
Neutral
Sensor
18
Courtesy of NationalSwitchgear.com