SECTION
7
INSTALLING
THE
PROGRAMMER
The
programmer
is
attached
to
the
bracket
mounted
to
the
left
side
of
the
breaker
s
center
channel
.
The
guide
pins
on
this
bracket
mate
with
the
holes
on
either
side
of
the
programmer
box
.
The
guide
pins
provide
the
necessary
alignment
for
the
connector
engagement
.
The
locking
lever
en
-
gages
with
the
pin
,
which
is
assembled
to
the
pro
-
grammer
frame
,
and
secures
the
programmer
to
the
mounting
bracket
.
TYPE
AK
-
50
,
AKS
-
50
BREAKERS
The
AKS
-
50
mounting
bracket
is
shown
in
Fig
.
7
-
1
.
To
install
:
Step
1
.
Insert
the
guide
pins
into
the
hole
and
push
on
the
programmer
.
This
will
engage
the
connectors
and
release
the
locking
lever
which
will
move
upwards
.
Step
2
.
Verify
that
the
locking
lever
actually
engaged
the
programmer
pin
.
To
remove
the
programmer
,
move
locking
lever
to
horizontal
position
,
thus
releasing
the
programmer
pin
.
Then
,
remove
the
programmer
.
TYPE
AK
-
75
,
AK
-
100
BREAKERS
The
AK
-
75
,
.
AK
-
100
mounting
bracket
is
shown
in
Fig
.
7
-
2
.
To
install
:
Step
1
.
Insert
the
guide
pins
into
the
holes
and
push
the
programmer
,
engaging
the
connectors
.
Step
2
.
Release
the
locking
lever
,
securing
the
program
-
mer
.
Step
3
.
Verify
that
the
locking
lever
actually
engaged
the
programmer
pin
.
To
remove
the
programmer
,
pull
out
the
locking
le
-
ver
,
wThich
will
release
the
programmer
pin
.
Then
remove
.
Fig
.
7
-
2
.
Programmer
Installed
22