EasyManua.ls Logo

GE MicroVersaTripPlus AK-50 - Page 24

GE MicroVersaTripPlus AK-50
26 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SECTION
8
TESTING
AND
TROUBLESHOOTING
Table
8
-
1
.
Resistance
Values
Resistance
in
Ohms
between
Common
and
Tap
Terminals
Breaker
Frame
Size
Ampere
Tap
FALSE
TRIPPING
BREAKERS
EQUIPPED
WITH
GROUND
FAULT
(
CONT
D
)
300
20
-
24
27
-
32
42
-
50
58
-
68
42
-
50
58
-
68
93
-
109
130
-
154
Step
4
.
On
ground
fault
breakers
serving
four
-
wire
loads
,
check
that
the
neutral
sensor
is
properly
connected
.
See
cabling
diagram
Fig
.
8
-
1
.
In
particular
,
the
fol
-
lowing
:
400
600
AK
-
50
AKS
-
50
800
600
Verify
that
the
neutral
sensor
has
the
same
rat
-
ing
and
tap
setting
as
the
phase
sensors
.
Check
continuity
between
the
neutral
sensor
and
its
equipment
-
mounted
secondary
discon
-
nect
block
.
Also
check
for
continuity
from
the
breaker
-
mounted
neutral
secondary
disconnect
block
through
to
the
female
harness
connector
.
If
the
breaker
s
lowrer
studs
connect
to
the
sup
-
ply
source
,
then
the
neutral
sensor
must
have
its
load
end
connected
to
the
source
.
See
Fig
.
8
-
1
.
Make
sure
that
the
neutral
conductor
is
carrying
only
that
neutral
current
associated
with
the
breaker
s
load
current
(
neutral
not
shared
with
other
loads
.
)
800
A
.
1200
B
.
1600
1200
20
-
24
28
-
34
37
-
44
61
-
72
AK
-
75
1600
2000
C
.
3000
1600
36
-
43
47
-
55
75
-
88
108
-
127
AK
-
100
2000
D
.
3000
4000
Step
5
.
If
the
preceding
steps
fail
to
identify
the
problem
,
then
measure
the
sensor
resistances
.
Since
the
phase
and
neutral
sensors
are
electrically
identical
,
their
resistance
should
closely
agree
.
)
24
Courtesy of NationalSwitchgear.com

Related product manuals