SECTION
3
FRONT
FRAME
BREAKER
CONVERSION
FRONT
VIEWS
OF
BREAKER
The
front
frame
conversion
consists
of
the
following
:
1
.
Separation
of
the
front
and
back
breaker
frames
.
Refer
to
the
appropriate
installation
and
maintenance
manuals
supplied
with
the
break
-
ers
and
equipment
for
instructions
on
accom
-
plishing
the
separation
.
Copies
of
these
publica
-
tion
may
be
obtained
from
your
local
GE
sales
office
.
NOTE
that
AK
-
75
and
AK
-
100
breakers
do
not
need
to
be
separated
to
complete
the
conversion
.
2
.
Relocating
and
remounting
the
W
and
X
relays
on
AK
-
50
,
AK
-
75
,
AK
-
100
electrically
operated
breakers
with
EC
trip
devices
.
3
.
Installing
the
flux
shifter
and
trip
paddle
.
4
.
Installing
the
programmer
mounting
bracket
.
5
.
Installing
the
programmer
wire
harness
.
6
.
Installing
the
communication
wire
harness
(
when
required
)
.
X
/
a
cz
:
\
w
V
1
^
/
x
/
i
I
BEFORE
I
\
\
\
CD
CD
Relocating
,
remounting
W
and
X
Relays
a
.
Remove
the
W
Relay
and
install
the
mounting
bracket
supplied
with
the
conversion
kit
to
the
upper
left
side
of
the
front
frame
.
See
Fig
.
3
-
1
.
b
.
Remove
the
X
Relay
and
its
mounting
bracket
.
Use
the
new
bracket
supplied
with
the
conver
-
sion
kit
to
remount
the
X
Relay
in
its
existing
position
.
See
Fig
.
3
-
1
and
3
-
2
.
AFTER
Fig
.
3
-
1
.
Relocating
W
Relay
and
Remounting
X
Relay
Fig
.
3
-
2
.
New
W
and
X
Relay
Mounting
Bracket
Installation