SECTION
3
FRONT
FRAME
BREAKER
CONVERSION
Installing
the
Flux
Shifter
(
Cont
d
)
AKU
-
50
BREAKERS
ONLY
1
.
For
easier
installation
of
AKU
-
50
breakers
,
the
Open
Fuse
Lock
Out
(
OFLO
)
device
may
be
separated
from
the
breaker
to
allow
insertion
of
the
flux
shifter
.
To
do
this
,
remove
the
three
bolts
attaching
it
to
the
base
.
2
.
The
terminal
block
must
be
remounted
on
the
upper
left
hand
side
of
the
breaker
.
Certain
parts
,
(
not
provided
with
the
conversion
kit
)
,
and
tools
are
required
to
complete
this
task
:
Six
strips
of
14
AWG
wire
Wire
splice
12
butt
splices
Wire
labels
Drill
and
size
F
drill
bit
/
is
-
18
tap
Flathead
screwdriver
Two
r
/
i
6
-
18
bolts
and
lock
washers
To
remount
the
terminal
block
:
Step
1
.
Drill
and
tap
two
(
2
)
holes
for
the
Yi
6
-
18
nuts
.
See
Fig
.
3
-
6
for
hole
locations
.
Step
2
.
Separate
the
Open
Fuse
Lock
Out
(
OFLO
)
device
by
removing
the
three
bolts
shown
in
Fig
.
3
-
7
.
Step
3
.
Remove
the
wires
that
connect
the
(
OFLO
)
device
to
the
terminal
block
.
Step
4
.
Cut
the
wires
that
connect
to
the
coils
where
they
join
and
label
the
wires
.
Attach
butt
splices
to
all
twelve
open
ends
(
Fig
.
3
-
8
)
.
Fig
.
3
-
6
.
Terminal
Block
Mounting
Hole
Pattern
Fig
.
3
-
7
.
OFLO
Removal
Bolts
Fig
.
3
-
8
.
Wire
Connectors
with
Butt
Splices
6
Courtesy of NationalSwitchgear.com