EasyManua.ls Logo

GE MLJ1000 - Page 31

GE MLJ1000
42 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GEK - 105560
30
Going to settings sequence Going to readout sequence
Note:
N.A. Not applicable
TABLE 2 CONFIGURATION OF OUTPUTS
FUNCTION NAME FUNCTION OPERATION
PEr Close enable
25 Synchronism
27 Undervoltage
_dL Dead line
db_ Dead bus
F25 Fail to close
ALA Alarm
If while in Readout Sequence, the
ENTER
and
“+”
buttons, are pressed simultaneously, the word CAL
will appear briefly on the screen, followed immediately by the average value of the line and bus
voltages.
By applying a known voltage, for example 60 RMS, to both the line and bus inputs, the trimmer is
adjusted (see figure 5) until a reading of 60.0 on the display is obtained.
If we now press the
ENTER
button for a moment, we return to Readout Sequence.

Related product manuals