GE Power Management 469 Motor Management Relay 7-5
7 TESTING 7.2 HARDWARE FUNCTIONAL TESTING
7
Table 7–7: 120
NICKEL TEST
APPLIED
RESISTANCE
120
NICKEL
EXPECTED RTD
TEMPERATURE READING
MEASURED RTD TEMPERATURE
SELECT ONE: ____(
°
C ) ____(
°
F )
° CELSIUS ° FAHRENHEIT 1 2 3 4 5 6 7 8 9 10 11 12
86.17
–50°C –58°F
120.00
0°C 32°F
157.74
50°C 122°F
200.64
100°C 212°F
248.95
150°C 302°F
303.46
200°C 392°F
366.53
250°C 482°F
Table 7–8: 100
NICKEL TEST
APPLIED
RESISTANCE
100
NICKEL
EXPECTED RTD
TEMPERATURE READING
MEASURED RTD TEMPERATURE
SELECT ONE: ____(
°
C ) ____(
°
F )
° CELSIUS ° FAHRENHEIT 1 2 3 4 5 6 7 8 9 10 11 12
71.81
–50°C –58°F
100.00
0°C 32°F
131.45
50°C 122°F
167.20
100°C 212°F
207.45
150°C 302°F
252.88
200°C 392°F
305.44
250°C 482°F
Table 7–9: 10
COPPER TEST
APPLIED
RESISTANCE
10
COPPER
EXPECTED RTD
TEMPERATURE READING
MEASURED RTD TEMPERATURE
SELECT ONE: ____(
°
C ) ____(
°
F )
° CELSIUS ° FAHRENHEIT 1 2 3 4 5 6 7 8 9 10 11 12
7.10
–50°C –58°F
9.04
0°C 32°F
10.97
50°C 122°F
12.90
100°C 212°F
14.83
150°C 302°F
16.78
200°C 392°F
18.73
250°C 482°F