GE Power Management 469 Motor Management Relay 4-29
4 SETPOINT PROGRAMMING 4.6 S5 THERMAL MODEL
4
4.6.3 OVERLOAD CURVE SETUP
y
O/L CURVE SETUP
y
[ENTER] for more
STANDARD OVERLOAD
CURVE NUMBER: 4
Range: 1 to 15; Step 1
Message seen only if Standard Curve Style is selected.
TIME TO TRIP AT
1.01 x FLA: 17414.5 s
Range: 0.5 to 99999.9 s; Step 1
Cannot be altered if Standard Curve Style is selected.
TIME TO TRIP AT
1.05 x FLA: 3414.9 s
Range: 0.5 to 99999.9 s; Step 1
Cannot be altered if Standard Curve Style is selected.
TIME TO TRIP AT
1.10 x FLA: 1666.7 s
Range: 0.5 to 99999.9 s; Step 1
Cannot be altered if Standard Curve Style is selected.
TIME TO TRIP AT
1.20 x FLA: 795.4 s
Range: 0.5 to 99999.9 s; Step 1
Cannot be altered if Standard Curve Style is selected.
TIME TO TRIP AT
1.30 x FLA: 507.2 s
Range: 0.5 to 99999.9 s; Step 1
Cannot be altered if Standard Curve Style is selected.
TIME TO TRIP AT
1.40 x FLA: 364.6 s
Range: 0.5 to 99999.9 s; Step 1
Cannot be altered if Standard Curve Style is selected.
TIME TO TRIP AT
1.50 x FLA: 280.0 s
Range: 0.5 to 99999.9 s; Step 1
Cannot be altered if Standard Curve Style is selected.
TIME TO TRIP AT
1.75 x FLA: 169.7 s
Range: 0.5 to 99999.9 s; Step 1
Cannot be altered if Standard Curve Style is selected.
TIME TO TRIP AT
2.00 x FLA: 116.6 s
Range: 0.5 to 99999.9 s; Step 1
Cannot be altered if Standard Curve Style is selected.
TIME TO TRIP AT
2.25 x FLA: 86.1 s
Range: 0.5 to 99999.9 s; Step 1
Cannot be altered if Standard Curve Style is selected.
TIME TO TRIP AT
2.50 x FLA: 66.6 s
Range: 0.5 to 99999.9 s; Step 1
Cannot be altered if Standard Curve Style is selected.
TIME TO TRIP AT
2.75 x FLA: 53.3 s
Range: 0.5 to 99999.9 s; Step 1
Cannot be altered if Standard Curve Style is selected.
TIME TO TRIP AT
3.00 x FLA: 43.7 s
Range: 0.5 to 99999.9 s; Step 1
Cannot be altered if Standard Curve Style is selected.
TIME TO TRIP AT
3.25 x FLA: 36.6 s
Range: 0.5 to 99999.9 s; Step 1
Cannot be altered if Standard Curve Style is selected.
TIME TO TRIP AT
3.50 x FLA: 31.1 s
Range: 0.5 to 99999.9 s; Step 1
Cannot be altered if Standard Curve Style is selected.
TIME TO TRIP AT
3.75 x FLA: 26.8 s
Range: 0.5 to 99999.9 s; Step 1
Cannot be altered if Standard Curve Style is selected.
TIME TO TRIP AT
4.00 x FLA: 23.3 s
Range: 0.5 to 99999.9 s; Step 1
Cannot be altered if Standard Curve Style is selected.
TIME TO TRIP AT
4.25 x FLA: 20.5 s
Range: 0.5 to 99999.9 s; Step 1
Cannot be altered if Standard Curve Style is selected.
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE

Table of Contents

Related product manuals