18 
11.8—Lubrication 
Proper lubrication is important for maintaining reliable circuit 
breaker performance. The ML-20 mechanism uses bearings 
which have a synthetic lining in some locations. These 
bearings do not require lubrication to maintain low friction, but 
lubrication does not harm them and oiling lightly is 
recommended. Sleeve bearings are used in some linkage 
locations and needle or roller bearings are used for low friction 
on trip shaft and close shaft. 
 
Bearings are lubricated during factory assembly with grease 
and oil, but all lubricants have a tendency to deteriorate with 
age. Providing a fresh lubricant supply at periodic intervals is 
essential to proper breaker operation, especially where 
frequent operation may have forced lubricant out of the 
bearing surfaces. Apply a few drops of light synthetic machine 
oil such as Mobile 1 at each bearing. Apply a coat of 
0282A2048P009 grease on the four corners of the closing 
spring guide where it enters inside the spring. 
 
Metal-to-metal contact surfaces should be cleaned and 
lubricated with 0282A2048P009 grease to provide cleanliness 
and prevent oxidation. 
 
Electrical primary contact surfaces also require periodic 
lubrication to inhibit oxidation and minimize friction. At each 
inspection and maintenance interval, do the following: 
 
1.  Wipe clean and coat lightly with grease 
(0282A2048P009) all silvered primary contact surfaces 
such as the movable contact rod of the interrupter and 
the primary disconnect fingers. 
 
2.  Clean and coat lightly with grease the pins of the 
secondary disconnect coupler. 
 
 
 
 
11.9—Recommended Maintenance 
The following operations should be performed at each 
maintenance check: 
1.  Perform a visual inspection of the breaker. Check for 
loose or damaged parts. 
 
2.  Perform slow closing operation described under 
MECHANICAL CHECKING AND SLOW CLOSING. 
 
3.  Check the erosion indicator and the wipe and gap as 
described under DIMENSIONAL CHECKS. 
 
4.  Perform the vacuum interrupter integrity test as 
described under ELECTRICAL CHECKS. 
 
5.  Lubricate the breaker operating mechanism as described 
under LUBRICATION. 
 
6.  Check the electrical operation using the test cabinet (if 
available) or the test position in the metalclad switchgear. 
 
CAUTION: REPEATED OPERATIONS AT A RATE EXCEEDING 
TWO PER MINUTE MAY CAUSE CHARGING MOTOR 
OVERHEATING AND SUBSEQUENT MOTOR FAILURE. 
 
7.  Examine the movable contact rod of the vacuum 
interrupter. With the breaker open, wipe the lubricant off 
the rod and examine the silver surface. The rod should 
have a burnished appearance without copper appearing 
through the silver. If copper is visible at more than one 
location per pole, or if the silver plating is torn, the 
interrupter assembly should be replaced. Re-lubricate 
movable contact rod with 0282A2048P009 grease 
 
8.   If desired, perform the additional electrical tests (Megger, 
Primary and Secondary High Potential, and Primary Circuit 
Resistance). See ELECTRICAL CHECKS. 
 
 
 
 
 
Nominal  Charge Motor  Close Coil  Trip Coil 
Control 
Voltage 
 
Part No. 
 
Range 
 
Part No. 
 
Range 
Part No. 
(5 cycle) 
Part No. 
(3 cycle) 
 
Range 
48 VDC  0177C5050G009  36-56  0209B8103G008  38-56  0209B8104G001  0209B8104G0
01 
28-56 
125 VDC  0177C5050G007  90-140  0209B8103G009  100-140  0209B8104G002  0209B8104G0
07 
70-140 
250 VDC  0177C5050G008  180-280  0209B8103G010  200-280  0209B8104G003  0209B8104G0
0…6 
140-280 
120 VAC  0177C5050G047  104-127  0209B8103G011*  104-127  0209B8104G004**  N/A  (Cap. Trip) 
104-127 
 
240 VAC 
 
0177C5050G008 
 
208-254 
 
0209B8103G012* 
 
209-254 
 
0209B8104G004** 
 
N/A 
(Cap. Trip) 
208-254 
 *With rectifier 
  **With Capacitor Trip Module 
 
Table 1.  Control Devices and Voltages