SECTION 13—Opening and Closing Speed
The opening speed is modified by moving the spring adjusting
nuts on the opening spring assemblies. A change in opening
speed affects the closing speed. Reference Figure 12.
The operating speeds for a 5 cycle breaker are as follows:
Operation
OperationOperation
Operation
Feet Per Second
Feet Per SecondFeet Per Second
Feet Per Second
Open 4.3 - 5.6
Close 2.6 – 3.9
V.I. STOP CENTER PHASE