EasyManua.ls Logo

GE STD16C - CURRENT TRANSFORMER RATIO ERROR

GE STD16C
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GEK-45307
For
Delta-connected
CTs
Tap
Current
=
LnL
N
where
N
is
the
number
of
CT
secondary
turns.
4.
Check
the
matching
of
relay
currents
to
relay
taps,
to
keep
the
mismatch
error
as
low
as
possible.
Calculate
the
percentage
of
mismatch
as
follows:
on
two—winding
transformers,
determine
the
ratio
of
the
two
relay
currents
and
the
tap
values
selected.
The
differences
between
these
ratios,
divided
by
the
smaller
ratio,
is
the
percent
of
mismatch.
The
mismatch
normally
should
not
exceed
5%.
For
three-winding
transformers,
the
percent of
mismatch
error
should
be
checked
for
all
combinations
of
currents
or
taps.
If
taps
cannot
be
selected
to
keep
this
percentage
error
within
allowable
limits,
it
will
be
necessary
to
choose
a
different
CT
ratio
on
one
or
more
lines,
to
obtain
a
better
match
between
relay
currents
and
relay
taps.
5.
Check
to
see
that
the
sum
of
the
relay
currents
that
will
be
applied
to
the
relay
for
a
fault
at
the
terminals
of
the
power
transformer
is
less
than
220
amperes
RMS
for
1
second.
If
the
period
during
which
a
fault
current
flows
in
the
relay
can
be
definitely
limited
to
a
shorter
time,
a
higher
current
can
be
accommodated
in
accordance
with
the
relation:
(Amperes)?
x
seconds
48,400
Also
check
that
the
suni
of
the
multiples
of
tap
current
on
an
internal
or
external
fault
do
not
exceed
150.
CURRENT
TRANSFORMER
RATIO
ERROR
The
CT
ratio
error
must
be
less
than
20%
at
8
times
relay
rated
tap
current.
This
is
based
on
the
instantaneous
unit
being
set
at
its
normal
setting,
which
is
8
times
tap
rating.
If
the
instantaneous
unit
pickup
is
raised
above
this
value,
the
20%
figure
must
be
reduced,
as
described
in
the
CHARACTERISTICS
section.
The
calculations
listed
below
are
for
the
worst—fault
condition,
as
far
as
CT
performance
is
concerned,
which
is
an
internal
ground
fault
between
the
CT
and
the
transformer
winding,
with
none
of
the
fault
current
supplied
through
the
neutral
of
the
protected
transformer.
1.
Determine
the
burden
on
each
CT,
using
the
following
expressions:
a.
For
Wye-connected
CTs
=
+
Ne+2f
+
2R
Ohms
(Equation
1)
b.
For
Delta-connected
CTs
Z
=
2B
+
Ne
+
2f
+
2R
Ohms
(Equation
2)
1000
6

Related product manuals