EasyManuals Logo

GE Uninterruptible Power Supply User Manual

GE Uninterruptible Power Supply
10 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #8 background imageLoading...
Page #8 background image
GE
modifications reserved Page 8/10
OPM_VCL_XXX_0K4_1K5_XGB_V012 User manual - VCL Series UPS 400-1500VA V012 - GB
2.4 BATTERY REPLACEMENT PROCEDURE
(Qualified service personnel only)
1. Turn off the equipment that is connected to the output sockets of the UPS.
2. Turn off the UPS.
3. Unplug the UPS power cord from the AC wall outlet.
4. Unplug the equipment from the output sockets of the UPS.
5. Remove the 2 screws at the bottom side of the front panel (fig. 1.)
6. Slide the panel downward, off the UPS (fig. 2).
7. Disconnect the red and black DC wires from the battery terminals (fig. 3).
NOTE
: DO NOT short the battery wires.
8. Replace the battery.
9. Connect the battery wires to the battery terminals.
NOTE
: a small spark might occur, this is normal.
10. Reinstall the front panel (fig. 4).
11. Fasten the two screws (fig. 5).
General guidelines
1. When replacing the batteries, use only the same type and size battery.
2. Never short the battery terminals. Shorting may cause the battery to burn. When working with batteries remove
watches, rings or other metal objects and only use insulated tools.
3. Avoid charging in a sealed container.
4. Never dispose of batteries in a fire: they may explode.
5. Never disassemble or reassemble batteries; their contents (electrolyte) may be extremely toxic. If exposed to
electrolyte, wash immediately with plenty of water, if eye contact occurs flush with water and contact a physician.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Uninterruptible Power Supply and is the answer not in the manual?

GE Uninterruptible Power Supply Specifications

VCL400

Power IconPower
rating VA/W400/250
AC input voltage window170 ~ 280Vac
frequency50 / 60 Hz auto sensing
Battery IconBattery
battery type12V, sealed lead acid, maintenance free
number x capacity of battery1x4.5Ah
battery recharge time8 hours typical
Operating Environment IconOperating Environment
ambient temperature0°C ~ 40°C (+32°F ~ 104°F)
maximum relative humidity95% (non-condensing)
storage temperature-15°C ~55°C (+5°F ~ 131°F)
Weight and Dimensions IconWeight and Dimensions
net weight4.0 kg
dimensions220x112x222 mm

VCL600

Power IconPower
rating VA/W600/360
AC input voltage window170 ~ 280Vac
frequency50 / 60 Hz auto sensing
Battery IconBattery
battery type12V, sealed lead acid, maintenance free
number x capacity of battery1x7Ah
battery recharge time8 hours typical
Operating Environment IconOperating Environment
ambient temperature0°C ~ 40°C (+32°F ~ 104°F)
maximum relative humidity95% (non-condensing)
storage temperature-15°C ~55°C (+5°F ~ 131°F)
Weight and Dimensions IconWeight and Dimensions
net weight4.6 kg

VCL800

Power IconPower
rating VA/W800/480
AC input voltage window170 ~ 280Vac
frequency50 / 60 Hz auto sensing
Battery IconBattery
battery type12V, sealed lead acid, maintenance free
number x capacity of battery1x9Ah
battery recharge time8 hours typical
Operating Environment IconOperating Environment
ambient temperature0°C ~ 40°C (+32°F ~ 104°F)
maximum relative humidity95% (non-condensing)
storage temperature-15°C ~55°C (+5°F ~ 131°F)
Weight and Dimensions IconWeight and Dimensions
net weight5.6 kg

VCL1000

Power IconPower
rating VA/W1000/600
AC input voltage window170 ~ 280Vac
frequency50 / 60 Hz auto sensing
Battery IconBattery
battery type12V, sealed lead acid, maintenance free
number x capacity of battery2x7Ah
battery recharge time8 hours typical
Operating Environment IconOperating Environment
ambient temperature0°C ~ 40°C (+32°F ~ 104°F)
maximum relative humidity95% (non-condensing)
storage temperature-15°C ~55°C (+5°F ~ 131°F)
Weight and Dimensions IconWeight and Dimensions
net weight8.4 kg

VCL1500

Power IconPower
rating VA/W1500/900
AC input voltage window170 ~ 280Vac
frequency50 / 60 Hz auto sensing
Battery IconBattery
battery type12V, sealed lead acid, maintenance free
number x capacity of battery2x9Ah
battery recharge time8 hours typical
Operating Environment IconOperating Environment
ambient temperature0°C ~ 40°C (+32°F ~ 104°F)
maximum relative humidity95% (non-condensing)
storage temperature-15°C ~55°C (+5°F ~ 131°F)
Weight and Dimensions IconWeight and Dimensions
net weight10.3 kg

Related product manuals