Do you have a question about the GE Match and is the answer not in the manual?
voltage amperes | 2200 VA |
---|---|
watts with resistive load | 1540 W |
ac input voltage | 220 - 240 V |
maximum ac input voltage | 350 V |
minimum start-up ac voltage | 187 V |
input frequency | 50 Hz or 60 Hz |
input frequency range | nominal ± 5 Hz |
no-load power consumption | 15 W |
max. ac input current | 12 A |
ac input tcb | 16 A |
ac output voltage | 230 V |
output frequency | 50Hz or 60Hz |
output frequency stability | < ± 0.1Hz |
power factor | 0.7 |
nominal voltage | 36 Vdc |
---|---|
number x capacity of batteries | 6x7 Ah |
recharge current | 3.5 - 10 A |
battery recharge time for 90% capacity | 2 hours |
runtime at typical load (75%) | 7 minutes |
ambient temperature at std. runtime | -10 to +40°C |
---|---|
sound at 1 meter | < 35 dB(A) |
maximum relative humidity | 95% (non-condensing) |
weight of ups | 18.0 kg |
---|---|
weight of battery pack | 21.3 kg |
dimensions (hxwxd) | 225 x 185 x 485 mm |
voltage amperes | 3000 VA |
---|---|
watts with resistive load | 2100 W |
ac input voltage | 220 - 240 V |
maximum ac input voltage | 350 V |
minimum start-up ac voltage | 187 V |
input frequency | 50 Hz or 60 Hz |
input frequency range | nominal ± 5 Hz |
no-load power consumption | 15 W |
max. ac input current | 16 A |
ac input tcb | 16 A |
ac output voltage | 230 V |
output frequency | 50Hz or 60Hz |
output frequency stability | < ± 0.1Hz |
power factor | 0.7 |
nominal voltage | 48 Vdc |
---|---|
number x capacity of batteries | 8x7 Ah |
recharge current | 3.5 - 10 A |
battery recharge time for 90% capacity | 2 hours |
runtime at typical load (75%) | 7 minutes |
ambient temperature at std. runtime | -10 to +40°C |
---|---|
sound at 1 meter | < 35 dB(A) |
maximum relative humidity | 95% (non-condensing) |
weight of ups | 20.1 kg |
---|---|
weight of battery pack | 26.5 kg |
dimensions (hxwxd) | 225 x 185 x 485 mm |
Highlights critical safety warnings, including electrical shock risks and prohibition of user serviceability for UPS components.
Details requirements for installation, including power supply, outlet usage, environmental conditions, and ventilation.
Step-by-step guide for connecting the battery pack, output cords to equipment, and mains power cord.
Defines status indicators and priority levels for alarms, detailing front panel indications for various situations.
Provides detailed explanations for charger status, AVR active, battery operation, low battery, overload, and high temperature.
Provides a table of common problems, possible causes, and solutions for UPS malfunctions.