6-14 VersaMax Modules, Power Supplies and Carriers GFK-1504N
6
IC200ERM002
Expansion Receiver Module, Non-isolated
The non-isolated Expansion Receiver Module (IC200ERM002) interfaces an
expansion “rack” to a VersaMax PLC or VersaMax NIU I/O Station system. The
expansion rack can to include up to eight VersaMax I/O and special-purpose
modules. A VersaMax power supply installed on the Expansion Receiver
Module provides operating power for the modules in the expansion rack. This
module may be used without an Expansion Transmitter Module (IC200ETM001)
in the PLC or I/O Station if there is only one expansion rack in the system or if
the cable length is one meter or less. An Expansion Transmitter Module is
required if there are multiple expansion racks or for a longer cable. Maximum
cable length for this non-isolated module is 15 m.
ERM002
PWR
EXP RX
SCAN
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
EXP 1
EXP 2
IC200ERM002
EXPANSION RECEIVER
5
7
6
4
1
3
2
0
High speed bus expansion interface
Supports Hold Last State
System fault isolation
Three LEDs indicate module power status and expansion port status
No DIP switches to set, easy software configuration into PLC system
Power supply mounts directly to module
Differential or single-ended operation
The Expansion Receiver Module supports hold last state operation of the output
modules in the event of loss of communications with the CPU/NIU. It also
permits isolation and repair of a faulty module within a rack.