GFK-1504N Chapter 9 Discrete Mixed Modules 9-3
IC200MDD840
Mixed Module, 24 V DC Positive Logic Input 20 Points /
Output Relay 2.0 A 12 Points
Module Specifications
20 positive DC inputs, two groups of 10
12 Form A relay outputs, two groups of 6
User input/output to logic
(optical) and frame ground
Group to group
250 V AC continuous; 1500 V AC for 1 minute
250 V AC continuous; 1500 V AC for 1 minute
One LED per point shows individual point on/off state
OK LED indicates backplane power is present
Backplane current consumption
External power supply
0 to 125 V DC, 5/24/125 V DC nominal
0 to 265 V AC (47 to 63Hz), 120/240 V AC nominal
Compatibility
HW,FW vers.
All
0 to +30 V DC, +24 V DC nominal
On state voltage
Off state voltage
+15 to +30 V DC
0 to +5 V DC
On state current
Off state current
0ms, 1.0ms (default), or 7.0ms
Output voltage 0 to 125 V DC, 5/24/125 V DC nominal
0 or 265 V AC (47 to 63Hz), 120/240 V AC nominal
2.0A for 5 to 265 V AC max. (resistive), 8.0A max. per group
2.0A for 5 to 30 V DC max. (resistive), 8.0A max. per group
0.2 A for 31 to 125 V DC maximum (resistive)
Not applicable (open contact)
No internal fuses or snubbers
20 cycles per minute (inductive load)
Fixed coil, moving armature